62-11039
7-121
Alarm
NO.
Steps
ALARM / CAUSE
CORRECTIVE ACTION
247 CONFIGURATIONS 3 ERROR
•
TRIGGER–ON: There is an error in Configuration Group 3 that is stored in the microprocessor memory
•
UNIT CONTROL: Incorrect Configuration(s) will be automatically set for default value
•
UNIT CONTROL: Incorrect Configuration(s) will be automatically set for default value.
•
RESET CONDITION: Alarm may be manually reset via Keypad or by turning the unit off, then back on
again.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, the active alarm
should clear itself (see reset condition above). Operate the unit through the appropriate modes to see if any active
alarm occurs. Continue with the steps below as necessary.
1.
Check Configurations
a. Check Configurations
All must be set for selectable values
2.
Reset microprocessor
a. Turn RS off for 30 seconds, then turn
back on.
Microprocessor powers up OK
Valid number is present
b. Check for valid Configurations in Data
List.
Valid number is present.
Alarm is cleared
R l
i
c. Valid Configurations can not be
entered.
Replace microprocessor
248 CONFIGURATION MODE / HP2 ERROR
•
TRIGGER–ON: EEPROM configuration is out of range
GG
O
O co gu at o s out o a ge
•
UNIT CONTROL: Shutdown and alarm
•
RESET CONDITION: Auto Reset only when valid info is available for the microprocessor are entered.
Follow the steps below until a problem is found. Once a repair or correction has been made, clear the alarm(s). (See
Note 1) Operate the unit through the appropriate modes to see if any active alarm occurs. Continue with the steps
below as necessary.
1.
Check microprocessor
a. Check Setpoint setting
b Enter new Setpoint
Must be between --22
°
F to +89.6
°
F (--30
°
C to +32
°
C)
Must be between 22
°
F to +89 6
°
F ( 30
°
C to +32
°
C)
b. Enter new Setpoint
c. Check Functional Parameters
Must be between --22
°
F to +89.6
°
F (--30
°
C to +32
°
C)
All settings must be valid.
2.
Reset microprocessor
a. Turn RS off for 30 seconds, then turn
back on.
Microprocessor powers up OK
back on.
b. Alarm 248 remains active.
Replace microprocessor.
Содержание VECTOR 1800 MT
Страница 1: ......
Страница 2: ...OPERATION SERVICE MANUAL for VECTOR 1800 MT Trailer Multi Temp Refrigeration Units ...
Страница 19: ...1 5 62 11039 1 3 SAFETY DECALS ...
Страница 20: ...1 6 62 11039 62 03958 00 Heat Warning 62 03957 01 High Voltage 62 60280 00 Standby Safety ...
Страница 21: ...1 7 62 11039 ...
Страница 303: ...10 1 62 11039 ...
Страница 310: ...10 8 62 11039 BASED ON ENGINEERING SCHEMATIC 62 60926 REV G NEXT SHT ...
Страница 311: ...10 9 62 11039 FROM PREVIOUS SHT ...