7-76
62-11039
Alarm
NO.
Steps
ALARM / CAUSE
CORRECTIVE ACTION
P155 CHECK COOLANT TEMP SENSOR
•
TRIGGER–ON: Engine Coolant Temp Sensor is not within the maximum range of --58
°
F to +266
°
F
(--50
°
C to +130
°
C)
•
UNIT CONTROL: Engine and standby operation: pre trip will fail and display “PRE TRIP FAIL AND
•
UNIT CONTROL: Engine and standby operation: pre--trip will fail and display “PRE--TRIP FAIL AND
COMPLETED”.
•
RESET CONDITION: Auto Reset if pre--trip mode is started again, or alarm may be manually reset via
keypad or by turning the unit off, then back on again.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, clear the
alarm(s). (See Note 1) Operate the unit through the appropriate modes to see if any active alarm occurs. Continue
with the steps below as necessary.
1.
Check Engine Coolant Sensor
a. Inspect Engine Coolant Sensor &
connector
No damage to sensor
No moisture, damage or corrosion in connector
b. Check
Engine
Coolant
Sensor
resistance (See Note 4)
10,000 Ohms @ 77
°
F (25
°
C) [See manual for complete
table of temperatures and resistance values.]
2.
Check Engine Coolant Sensor Wiring
a. Inspect harness & control box
connector pins & terminals (See
wiring schematic)
No physical damage to harness.
No damaged or corroded pins
P156 CHECK BATTERY VOLTS
•
TRIGGER–ON: Battery voltage is less than 11 VDC or greater than 17 VDC
•
UNIT CONTROL: Engine and standby operation: pre--trip will fail and display “pre--trip FAIL AND
UNIT CONTROL: Engine and standby operation: pre trip will fail and display pre trip FAIL AND
COMPLETED”.
•
RESET CONDITION: Auto Reset if pre--trip mode is started again, or alarm may be manually reset via
keypad or by turning the unit off, then back on again.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, clear the
alarm(s). (See Note 1) Operate the unit through the appropriate modes to see if any active alarm occurs. Continue
with the steps below as necessary.
1.
Check for Battery Voltage Too High Alarm
a. Check for Alarm 15
Alarm conditions must be corrected and the alarm cleared
to continue.
Test battery charger output
Test battery condition
Check wiring connections between battery and battery
charger
2.
Check for Battery Voltage Too Low Alarm
a. Check for Alarm 16
Alarm conditions must be corrected and the alarm cleared
to continue.
Test battery charger output
Test battery condition
Check wiring connections between battery and battery
charger
Содержание VECTOR 1800 MT
Страница 1: ......
Страница 2: ...OPERATION SERVICE MANUAL for VECTOR 1800 MT Trailer Multi Temp Refrigeration Units ...
Страница 19: ...1 5 62 11039 1 3 SAFETY DECALS ...
Страница 20: ...1 6 62 11039 62 03958 00 Heat Warning 62 03957 01 High Voltage 62 60280 00 Standby Safety ...
Страница 21: ...1 7 62 11039 ...
Страница 303: ...10 1 62 11039 ...
Страница 310: ...10 8 62 11039 BASED ON ENGINEERING SCHEMATIC 62 60926 REV G NEXT SHT ...
Страница 311: ...10 9 62 11039 FROM PREVIOUS SHT ...