Alarm
NO.
Steps
ALARM / CAUSE
CORRECTIVE ACTION
245 MICRO SW REV ERROR
•
TRIGGER–ON: There is an error in the Microprocessor Revision Number that is stored in the
Microprocessor memory.
p
y
•
UNIT CONTROL: Alarm only
•
RESET CONDITION: Alarm may be manually reset via Keypad or by turning the unit off, then back on
again.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, the active alarm
should clear itself (see reset condition above). Operate the unit through the appropriate modes to see if any active
alarm occurs. Continue with the steps below as necessary.
1.
Check Microprocessor Software Revision
a. Check
Microprocessor
Software
Revision
Will be a 6 digit number
2.
Reset microprocessor
a. Turn RS off for 30 seconds, then turn
back on.
Microprocessor powers up OK
Valid number is present
b. Check for valid Configurations in Data
List.
Valid number is present.
Alarm is cleared
R l
i
c. Valid Configurations can not be
entered.
Replace microprocessor
246 EEPROM WRITE FAILURE
•
TRIGGER–ON: here is an error in the ability to write information to be stored in the memory.
•
UNIT CONTROL: Alarm only
•
UNIT CONTROL: Alarm only
•
RESET CONDITION: Alarm may be manually reset via Keypad or by turning the unit off, then back on
again.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, the active alarm
should clear itself (see reset condition above). Operate the unit through the appropriate modes to see if any active
alarm occurs. Continue with the steps below as necessary.
1.
Check Microprocessor
a. Check Setpoint setting
b.Enter new Setpoint
Must be between --22
°
F to +89.6
°
F (--30
°
C to +32
°
C)
Must be between --22
°
F to +89.6
°
F (--30
°
C to +32
°
C)
2.
Reset Microprocessor
a. Turn main switch off for 30 seconds,
then turn on.
Microprocessor powers up OK
then turn on.
b. Alarm 246 remains active.
Replace microprocessor
Содержание VECTOR 1800 MT
Страница 1: ......
Страница 2: ...OPERATION SERVICE MANUAL for VECTOR 1800 MT Trailer Multi Temp Refrigeration Units ...
Страница 19: ...1 5 62 11039 1 3 SAFETY DECALS ...
Страница 20: ...1 6 62 11039 62 03958 00 Heat Warning 62 03957 01 High Voltage 62 60280 00 Standby Safety ...
Страница 21: ...1 7 62 11039 ...
Страница 303: ...10 1 62 11039 ...
Страница 310: ...10 8 62 11039 BASED ON ENGINEERING SCHEMATIC 62 60926 REV G NEXT SHT ...
Страница 311: ...10 9 62 11039 FROM PREVIOUS SHT ...