5.5 SETTING PM (PREVENTATIVE MAINTENANCE) HOURMETERS
The programmable PM Hourmeters (PM1 – PM5) which
can be configured to count any of the following
•
Diesel Engine Hours
•
Standby Electric Motor Hours
•
Switch On Hours
•
Start Cycles
•
High Speed Hours
The PM Hourmeters are activated and the reset interval
is selected from the Configuration List. To turn on the
Engine PM Hourmeter, select the desired maintenance
interval (in hours), and enter as the
“DIESEL RESET VALUE” in the Configuration List.
Selecting OFF will completely turn the Engine PM
Hourmeter off. The reset value selected here will be the
value used when the PM Hourmeter is reset from the
Functional Parameter List.
To turn on the Switch On PM Hourmeter, select the
desired maintenance interval (in hours), and enter as
the “SWITCH ON RESET VALUE” in the Configuration
List. Selecting OFF will completely turn the Switch On
PM Hourmeter off.
To turn on any of the Programmable PM Hourmeters,
they must first be programmed to count one of the
available parameters from the list above. (For example,
PM 1 may be programmed to count start cycles.)
Selecting OFF will completely disable the PM
Hourmeter. Once a selection is made, then a reset
interval may be selected. For hours, the PM Hourmeter
may be set in 50 hour increments anywhere from 50 to
30,000 hours. For cycles, the PM Hourmeter may be
set in 1,000 cycle increments anywhere from 1,000 to
90,000 cycles. Selecting OFF instead of an interval will
also disable the PM Hourmeter.
Once the PM Hourmeters are activated from the
Configuration List, they can be turned OFF; once off the
operation can be RESUMED; or it can be RESET for a
new interval, all from the Functional Parameter List.
The PM Hourmeters for RESET may be reset using
either a PC or the Keypad. RESET is only available
when the accumulated hours are more than 95% of the
reset value for that Hourmeter. (For example: the
Engine PM Hourmeter Reset Interval is 1000 hrs. Reset
will be allowed anytime after 950 hours have expired.)
TIP
Factory default is OFF for all PM Hourmeters.
To change the PM Hourmeter to On and set the desired
number of hours:
1. From the Configuration List, select the
PM Hourmeter.
2. Press = to enter.
3. Now select the desired new interval.
4. Press = to enter.
5. Turn the Start/Run Off switch off then back to Start/
Run. Check the Data List. The correct number of
hours should be showing as
“HOURS TO ENGINE MAINT”.
Содержание VECTOR 1800 MT
Страница 1: ......
Страница 2: ...OPERATION SERVICE MANUAL for VECTOR 1800 MT Trailer Multi Temp Refrigeration Units ...
Страница 19: ...1 5 62 11039 1 3 SAFETY DECALS ...
Страница 20: ...1 6 62 11039 62 03958 00 Heat Warning 62 03957 01 High Voltage 62 60280 00 Standby Safety ...
Страница 21: ...1 7 62 11039 ...
Страница 303: ...10 1 62 11039 ...
Страница 310: ...10 8 62 11039 BASED ON ENGINEERING SCHEMATIC 62 60926 REV G NEXT SHT ...
Страница 311: ...10 9 62 11039 FROM PREVIOUS SHT ...