62-11039
7-15
Alarm
NO.
Steps
ALARM / CAUSE
CORRECTIVE ACTION
23
A/C CURRENT OVER LIMIT
•
TRIGGER ON: The high voltage amp draw is over the limit shown in the table below for more than
10 seconds.
Condition
1 Compartment
Enabled
2 Compartments
Enabled
3 Compartments
Enabled
Diesel High Speed Cool
30A
30A
30A
Diesel Low Speed or
Standby Cool
30A
30A
30A
Diesel High Speed Heat
18A
24A
28A
Diesel Low Speed or
Standby Heat
14A
20A
24A
Diesel High Speed Heat
Defrost
16A
22A
26A
Diesel Low Speed or
Standby Heat Defrost
12A
18A
22A
Diesel High Speed Null or
Fan Defrost
8A
10A
12A
Diesel Low Speed or
Standby Null or Fan De-
frost
6A
8A
9A