Chapter 5 Detailed Function Introductions
92
Tips:
The changed value of P0.02 by keypad digital encoder will be active immediately. If press "ENTER" key, the value
will be stored into the inverter
’
s internal EEPROM and will not be lost even power-off the inverter.
When P0.03is set to 1: if P3.18 is set to2, the changed value of P0.02 by keypad digital encoder will be saved when
power loss. Otherwise, the changed value will not be saved
P0.03 Frequency setting source 1
Setting range: 0~12 [1]
0: NULL
1: keypad digital setting, digital knob adjustment
2: Terminal AI1
3: Terminal AI2
4: Terminal AI3 (reserve for 3004GB and
below models)
5: Pulse input
6: Serial communication
7: Line speed(reserve)
8: Multi-step Speed
9: Terminal UP/DOWN
10: Programmable Logic Controller (PLC)
11: PID close-loop
12: Wobble frequency operating
P0.04 Frequency setting source 2
Setting range:: 0~9 [0]
0: NULL
1: keypad digital setting, digital knob adjustment
2: Terminal AI1
3: Terminal AI2
4: Terminal AI3 (reserve for 3004GB and
below models)
5: Pulse input
6: Serial communication
7: Line speed(reserve)
8: Multi-step Speed
9: torque slip compensation dosage
Notes:
If P0.03 is set to 1: During keypad digital setting, in monitoring state, the set frequency can be modified
through digital knob on the keypad; when the set frequency is related to P0.02, in monitoring state, value of
P0.02 can be adjusted through the keypad knob.
Terminal AI1, AI2 and AI3 are analog input signals. When using terminal AI1, AI2, the output frequency can
be adjusted through 0~10V voltage signal or 0~20mA current signal; when using terminal AI3, the output
frequency can be adjusted through - 10V~ 10V voltage signal or - 20mA~20mA current signal; negative
value represents reversing operation.
Signal type is selected through the relevant toggle switch on the control circuit board, and please refer to
Section 2.5 Wiring Instruction for Control Loop.
Corresponding relationship between sizes and frequencies of terminal AI1, AI2, AI3, and pulse input signal is
programmable; please see detailed descriptions of Group P4 parameters.
Serial communication setting, the user can connect the serial communication port to a PC or PLC. The set
frequency of the inverter is controlled by the communication mode.
When P0.03 is set to 9, see description of Group P3 UP / DOWN.
When P0.04 is set to 9, compensation is half of the corresponding slip frequency difference of the set torque
and the actual torque.
P0.05 Frequency setting combination 1
Setting range: 0
~9
[0]
P0.06 Frequency setting combination 2
Setting range: 0
~9
[0]
0: Frequency setting source 1
1: Frequency setting source 2
2: MIN(Frequency setting source 1
,
Frequency
3: MAX(Frequency setting source 1
,
Frequency setting