Chapter 5 Detailed Function Introductions
125
when switching between power frequencies and frequency conversion of multiple motor, as shown in Fig.
5-3-10.
Operating Freq.(Hz)
Frequency
upper limit
FDTH
Time
FDTL
Frequency
lower limit
FDTH Delay time
EDTL Delay time
Figure. 5-3-10 FDTH/FDTL
P3.31Torque detection reference
Setting range: 0.0~200.0% [100.0%]
Notes:
If motor torque is equal to or more than the range of torque detection reference, the output of terminal is
valid. If the motor torque is less than 80% of reference, the output of terminal is invalid, as shown in Figure.
5-3-11
Output torque
Torque detection
reference
Torque arriving
detection signal
Time
Torque detection
reference*80%
Torque arriving
detection
Fig. 5-3-11 Torque reaching detection
P3.32 Preset Count value
Setting range: 0~9999 [0]
Notes:
When the counter value is equal to this value, the terminal output is active, as shown in Fig. 5-3-12.
1
2
3
4
5
6
7
8
Xi Input
Counting value
arriving output
Preset Counting value
Figure. 5-3-12 Count value arriving