Chapter 5 Detailed Function Introductions
132
T1
T2
T3-T12
T13 T14
T15
运行命令
f1
f2
f3-f12
f13
f14
f15
运行频率(Hz)
时间
T1
T2
T13
T14 T15
f1
f2
f13
f14
f15
T1
T2
f1
f2
第一次循环
第二次循环
停机命令
T3-T12
f3-f12
Figure. 5-5-3 Continuous operation of PLC
P5.01 PLC restarting mode selection
Setting range: 0~2 [0]
0: Restart from first step
1: Continue from the step where the inverter stops
2: Continue to operate at the frequency when the
inverter stops
Notes:
Restart from first stage
If the inverter stops during PLC operation because of receiving stop command or fault, or power loss, it will
restart from the first step after restarting.
Continue from the step where the inverter stops
When the inverter stops during PLC operation because of
receiving stop command or fault, it will record the
operating time and will continue from the step where the inverter stops, and restart at the frequency defined for
this step, as shown in Figure.5-5-4
T1
T2
T3
T4
T6
T7
运行命令
f1
f2
f3
f4
f5
f6
f7
运行频率(Hz)
时间
中断时刻
从中断时刻的阶段频率继续运行
a1
a2
d3
a3
a4
d5
a5
a6
a7
阶段5已运行时间
阶段5剩余时间
Figure. 5-5-4 PLC start mode 1
Running frequency (Hz)
Time
First cycle
Second cycle
Run command
Stop command
Continue to run at the stage frequency at
the moment of interrupt
Running frequency (Hz)
The remaining time
of Phase 5
The run time of Phase 5
Run command
Interruption
time
Time