Chapter 5 Detailed Function Introductions
146
5.10 V/F Control (Group P9)
P9.00 V/F curves setting
Setting range: 0~4 [0]
0: Constant Torque Characteristic Curve 0
1: Reduction Torque Characteristic Curve 1 (2.0)
2: Reduction Torque Characteristic Curve 2
(1.5)
3: Reduction Torque Characteristic Curve 1 3 (1.2)
P9.01 V/F frequency value F1
Setting range: 0.0~P9.03 [10.00Hz]
P9.02 V/F voltage value V1
Setting range: 0~100.0% [20.0%]
P9.03V/F frequency value F2
Setting range: P9.01~P9.05 [25.00Hz]
P9.04 V/F voltage value V2
Setting range: 0~100.0% [50.0%]
P9.05 V/F frequency value F3
Setting range: P9.03~P0.09 [40.00Hz]
P9.06 V/F voltage value V3
Setting range: 0~100.0% [80.0%]
Notes:
This group of function codes define the flexible V/F setting manner of the series frequency inverter to satisfy
the different load characteristic needs.
Figure 5-9-1 Torque-reducing curve
When 4 is selected for P9.00, the user can self-define the V/F curve through P9.01~P9.06. As showed in
Figure 5-9-2, the V/F curve is defined with the four-point broken line to be adapted for the special load
characteristics. Notes: V1<V2<V3. In the case of low frequency, if the voltage is set to be too high, the
motor may be overheated and even burned, and the frequency inverter may stall over current or be
over-current protected.