Chapter 5 Detailed Function Introductions
163
Notes:
Only three faults including OC, Ou and GF can be reset automatically.
The three faults in operation can be reset automatically according to the set times Pd.18 and interval Pd.19.
During the resetting interval, output is blocked and the inverter operates with zero frequency. The inverter
will operate with the startup manner after automatic resetting is finished. When Pd.18 is set as 0, it means that
there is not the function of automatic resetting, and protection should be done immediately.
Tips:
Be careful in using auto-reset function, otherwise human injury or material loss may occur.
SC fault need 10 seconds waiting time for manual reset.
Pd.21Operation protection when power on
Setting range: 0.1 [0]
0: No protection
1: Protection
Pd.22Operation protection after operation command
given mode switching
Setting range: 0.1 [0]
0: Continuous operation
1: Stopping, restart to operate when receive new
operation command
Explanation:
When Pd.21 is set to 1, it is the power-on operation protection, namely direct power when the operation
commands are valid. Frequency inverter will be powered on protection, until receive operation command
again, the frequency inverter will work.
When the Pd.22 command switches the operation protection setting to 1, when the frequency inverter is in a
stopping state, after run command given mode switching, frequency inverter will not immediately run until
receive operation command again. When the frequency inverter is in an operation state, command switch, the
frequency inverter will slow down, until receive operation command.
Pd.23 Action selection when rotor blocked (reserve)
Setting range: 0.1 [0]
0: No execute anti-blocking rotation action serials
1: Execute anti-blocking rotation action serials
Pd.24
Rotor-blocking
action
trigger
condition
(reserve)
Setting range: 0~3 [2]
0: Output current over triggering level
1: Control terminal close
2: Output current over setting or control terminal close
3: Timing execute periodically
Pd.25 Stalling Action Triggering Level (Reserved)
Setting range:100.0%~300.0% [200%]
Pd.26 Stalling Action Triggering Period (Reserved)
Setting range:0.00h~200.0h [0.00h]
Pd.27 Positive Step Frequency (Reserved)
Setting
range:0.00Hz~Frequency
upper
limit
[0.00Hz]
Pd.28 Positive Step Duration (Reserved)
Setting range:0.0s~1000s [0.0s]
Pd.29 Negative Step Frequency (Reserved)
Setting
range:0.00Hz~Frequency
upper
limit
[0.00Hz]
Pd.30 Negative Step Duration (Reserved)
Setting range:0.0s~1000s [0.0s]
Pd.31 Interval between Positive Step and Negative
Step (Reserved)
Setting range:0.0s~1000s [0.0s]
Pd.32 Step Action Repetition Times (Reserved)
Setting range:0~100 [0]
Pd.33 Software Current-limiting Point
Setting Range:100.0%~250.0%
Pd.34 Hardware Current-limiting Enabled
Setting Ranged:0,1 [1]
0: Prohibited
1: Allowed
Notes:
The software current-limiting point 100.0% corresponds to the rating current of frequency inverter.
The hardware current-limiting point is fixed as 160.0% of the rating current of frequency inverter. The
specific value is related to the inverter type.