Chapter 5 Detailed Function Introductions
117
EI0 - External interrupt signal normally open / EI1 - External
interrupt signal normally close: During
operating, the inverter stops its output and runs at zero-speed when it receives external interrupt signal. Once
the signal is removed, the inverter will start and resume normal operation. Please refer to note of EH0 and
EH1 above. As shown in Figure. 5-3-6.
KM
Xj(External fault signal
/External interrupt signal
input )
Xi(External fault signal
/External interrupt signal
input)
Fault relay
COM
Figure. 5-3-6 Normally open / normally close
41: StoppingStopping plus DC brake
Use the terminal to DC brake on the system in the stoppingstopping state to prevent motor malfunction.
42~44: Terminal PLC Control
PLC input: Program timing running. Replace the frequency setting 1 with PLC; wobble frequency input / PID
input is the same. When using frequency setting source 2, PLC input is inactive.
PLC pause: Pause the program timing running. When the terminal is active, pause the program timing
running, and the inverter runs at 0 frequency; it will continue running at the breakpoint after canceling the
pause instruction. When pressing "STOP" key during effective period of the terminal, the program running
counter is cleared, it needs to start in the start-up mode when starting up next time. If the inverter does not
work under program run mode, then the function is meaningless.
PLC stoppingstopping reset: stoppingstopping state under the PLC operating mode, when the function
terminal is active, the running phase, running time and other information remembered at the time of
stoppingstopping of PLC will be cleared.
45~46: Terminal wobble frequency running
Wobble frequency input: Wobble frequency running, replace the frequency setting 1 with wobble frequency
running. When using frequency setting source 2, wobble frequency input is inactive.
Reset the wobble frequency operating status: In stop state of wobble frequency operation, the valid terminal
can clear the wobble frequency operating information memorized in stop.
47: Terminal PID operation
PID input: PID running, replacing the frequency setting 1 with PID closed loop. When using frequency
setting source 2, PID input is inactive
48: Speed/torque mode switch,
In the vector control mode, set by P8.10 torque control mode. When the terminal is set and valid, torque mode
will automatically switch. For example: when P8.10 is set to 0 (according to the speed mode), when the
terminal is set to 48 and valid, the operation mode is automatically switched to the torque mode.
49.53: Timing drive input
If the 49 terminal is valid, start the timing, else zero-clear.
If the timing arrives at preset setting of P3.33, stop timing. As shown in Figure.5-3-7:
When the 53 terminal is valid, the unit of P3.33(preset of timing arriving) will be minutes, or it will be
second.