Chapter 5 Detailed Function Introductions
126
P3.33 Preset timing arriving
Setting range: 0.0~6553.0 [0.0]
Notes:
When the timing is equal to this value, the terminal output is active, as shown in Fig. 5-3-7.
The unit of P3.33 timing is identified by function terminal 53; the cumulative time of timing is cleared only
when terminal 49 is inactive, otherwise it remains original.
P3.34 Preset operating time
Setting range: 0~65530h [65530]
Notes:
When the total operating time reaches the preset operating time (P3.26), the output of terminal is valid.
P3.35 underload detection set value
Setting range: 0 ~ 200.0 % [10.0 %]
P3.36 underload detection terminal output delay
time
Setting range: 0 ~ 100.0s [5.0s]
Notes:
P3.35 Underload detection set point 0~200.0% corresponds to 0 ~ 2 times of the rated torque. When the
actual output torque is less than P3.35 set point, the terminal has output if the underload detection terminal
setting is active after P3.36 (underload detection terminal output delay time); when the torque increases and is
greater than the set point of P3.35, the terminal output is inactive.
5.5 Analog and pulse function (Group P4)
P4.00 Analog Nonlinear Selection
Setting range: 0~3 [0]
0: Null
1: AI1
2: AI2
3: Pulse
Notes:
If the setting is 0, P4.01~P4.05 are used to define AI1 inputs, P4.06~P4.10 are used to define AI2 inputs, and
P4.11~P4.15 are used to defined pulse inputs. They are independent and have no interference with each other.
If the setting is not 0, it will be nonlinear selection, all the parameters from
P4.01 to P4.15 are setting points
for the selected channel by P4.00. The filter time according to the selected channel setting and the physical
value of the others are 0.
If the setting of P4.00 is 1 or 2, the selection will be analog input and the default values to each channel
arranged from small to great are: 0.00V, 2.00V, 4.00V, 6.00V, 8.00V, 10.00V;
If the setting is 3, the selection will be pulse input. While the default input to the channel are: 0.00 kHz, 10.00
kHz, 20.00 kHz, 30.00 kHz, 40.00 kHz, and 50.00 kHz. The default physical values are linear relation.
Tips: Only when the value of P4.00 is changed and saved by pressing the “ENTER” key, the input channel value can
be initialized to the default value.
P4.01 AI1 Minimum analog input value)
Setting range: 0.0~P4.03 [0.00V]
P4.02 Corresponding physical quantity of input value of
AI1 minimum analog
Setting range: -100.0%~100.0% [0.0%]
P4.03 AI1 maximum analog input value
Setting range: P4.01~10.00V [10.00V]
P4.04 Corresponding physical quantity of input value of
AI1 maximum analog
Setting range: -100.0%~100.0% [100.0%]
P4.05 AI1 Analog input filter time constant
Setting range: 0.01~50.00s [0.05s]
P4.06 AI2 Minimum analog input value
Setting range: 0.00~P4.08 [0.00V]
P4.07 Corresponding physical quantity of input value of
AI2 minimum analog
Setting range: -100.0%~100.0% [0.0%]
P4.08 AI2 Maximum analog input value
Setting range: P4.06~10.00V [10.00V]
P4.09 Corresponding physical quantity of input value of
Setting range: -100.0%~100.0% [100.0%]