![Alpha 6000S series Скачать руководство пользователя страница 68](http://html1.mh-extra.com/html/alpha/6000s-series/6000s-series_user-manual_2905269068.webp)
Chapter 4 Parameter Index
67
P4: Analog and pulse input and output terminals
Function
code
Parameter
LCD display
Setting range
Factory
setting
Mod.
MODBUS
address
P4.00
Analog nonlinear
selection
Analog
nonlinear
selection
0: No 1: AI1
2: AI2 3: Pulse
0
×
0500
P4.01
Input value of AI1
minimum analog
AI1 minimum
analog
0.00~P4.03
0.00V
○
0501
P4.02
Corresponding
physical quantity of
input value of AI1
minimum analog
Minimum
corresponding
physical quantity
of AI1
-100.0%~100.0%
0.0%
○
0502
P4.03
Input value of AI1
maximum analog
AI1 maximum
analog
P4.01~10.00V
10.00V
○
0503
P4.04
Corresponding
physical quantity of
input value of AI1
maximum analog
Maximum
corresponding
physical quantity
of AI1
-100.0%~100.0%
100.0%
○
0504
P4.05
AI1 input filter time
constant
AI1 input filter
time
0.01~50.00s
0.05s
○
0505
P4.06
Input value of AI2
minimum analog
AI2 minimum
analog
0.00~P4.08
0.00V
○
0506
P4.07
Corresponding
physical quantity of
input value of AI2
minimum analog
Minimum
corresponding
physical quantity
of AI2
-100.0%~100.0%
0.0%
○
0507
P4.08
Input value of AI2
maximum analog
AI2 maximum
analog
P4.06~10.00V
10.00V
○
0508
P4.09
Corresponding
physical quantity of
input value of AI2
maximum analog
Maximum
corresponding
physical quantity
of AI2
-100.0%~100.0%
100.0%
○
0509
P4.10
AI2 input filter time
constant
AI2 input filter
time
0.01~50.00s
0.05s
○
050A
P4.11
Minimum pulse input
value
Minimum pulse
input value
0.00~P4.13
0.00
kHz
○
050B
P4.12
Corresponding
physical quantity of
input value of
minimum pulse
quantity
Corresponding
physical quantity
of minimum
pulse quantity
input
-100.0%~100.0%
0.0%
○
050C
P4.13
Input value of
maximum pulse
quantity
Input value of
maximum pulse
quantity
P4.11~50.00kHz
50.00
kHz
○
050D
P4.14
Corresponding
physical quantity of
input value of
maximum pulse
quantity
Corresponding
physical quantity
of maximum
pulse quantity
input
-100.0%~100.0%
100.0%
○
050E
P4.15
Pulse input filter time
Pulse input filter
time
0.01~50.00s
0.05s
○
050F
P4.16
Input value of AI3
minimum analog
AI3 minimum
analog
-10.00V~P4.18
Reserve for 3004GB
and below models
0.00V
○
0510
Содержание 6000S series
Страница 1: ......
Страница 74: ...Chapter 4 Parameter Index 73 P6 18 Stochastic swing ratio MIN Stochastic swing ratio MIN 0 1 10 0 0 1 0712...