Chapter 5 Detailed Function Introductions
104
5.3 Auxiliary Operation (Group P2)
P2.00 Jog Frequency
Setting range: 0.10~Frequency upper limit [5.00Hz]
P2.01 Acc time of Jog
Setting range: 0.1~3600s [6.0/20.0s]
P2.02 Dec time of Jog
Setting range: 0.0~3600s [6.0/20.0s]
Notes:
P2.00~P2.02 define the related parameters of Jog.
As shown in Figure. 5-2-1, t1 is Acc time of Jog and t3 is Dec time of Jog t2 is the Jog time; P2.00 is the Jog
frequency.
Actual Acc time of JOG (t1) can be determined by the following formula. So does the actual Dec time of JOG
(t3).
JOG stop mode depends the value of P2.02: If P2.02 setting is not 0, the motor will stop as stop mode 0; if
P2.02 setting is 0, the motor will coast to stop
Operation Freq.(Hz)
P2.00
JOG Command
Time
t
2
t
1
t
3
t
1
=
P2.00×
P2.01
P0.07
Fig. 5-2-1 Description of Jog parameters
Tips:
1. In Jog operation, the inverter starts according to starting mode 0. The unit of Acc/Dec time is second.
2. If deceleration time of Jog is 0: coast-to-stop, but DC braking terminal takes effect when stop Jog
operation, the deceleration time will be P2.23 Dec time 4.
3. Jog operation can be controlled by keypad, terminals or serial port.
P2.03 Switching time between run forward
and reverse
Setting range: 0.0~3600s [0.0s]
Notes:
The delay time is the transition time at zero frequency when the inverter switching its running direction as
shown in Figure. 5-2-2 as t1.