Chapter 5 Detailed Function Introductions
164
Compared with the software current-limiting function, hardware current-limiting responds more quickly.
Thus, it is suggested that hardware current-limiting function not be cancelled.
5.15 Running History Record (Group PE)
PE.00 Type of latest fault
Setting range: Table 5-14-1 [NULL]
PE.01 Output frequency at last fault
Setting range: 0~Frequency upper limit [0.00Hz]
PE.02 Reference frequency at last fault
Setting range: 0~Frequency upper limit [0.00Hz]
PE.03 Output current at last fault
Setting range: 0~2 times of (rated current) [0.0A]
PE.04 DC bus voltage at last fault
Setting range: 0~1000V [0V]
Notes:
If the frequency inverter fails during operation, the PWM output will be blocked immediately to enter the
fault protection state and the fault indicator light TRIP will be flickering. For working conditions during the
time of fault (e.g. output frequency, set frequency, output current, and DC busbar voltage, etc) and the fault
content of recent three times can be found in the function code PE.01~PE.08. Instruction of fault types is
showed in Table 5-14-1:
Table 5-14-1 Instruction of Fault Types
Fault
code
Description
Fault
code
Fault categories
NULL
No fault
Uu1
Bus Under voltage
Uu2
Control circuit Under voltage
Uu3
MC fault
OC1
Over current in Acc process
OC2
Over current in Dec process
OC3
Over current in constant speed Operation
Ou1
Over Voltage in Acc process
Ou2
Over Voltage in Dec process
Ou3
Over voltage in constant speed operation
GF
Ground Fault
OH1
Heat-sink Overheat
OL1
Motor Overload
OL2
Inverter Overload
SC
Load Short-Circuit
EFO
External Fault of serial communication
EF1
External Fault of terminal
SP1
Input phase failure or Unbalance
SPO
Output phase failure or Unbalance
CCF1
Control Circuit Fault 1: Transmission
between the inverter and keypad cannot
be established 5 seconds after supplying
power.
CCF2
Control circuit fault 2: Transmission between
the inverter and keypad is established once
after supplying power, but later transmission
fault continues for more than 2 seconds.
CCF3
EEPROM Fault
CCF4
AD Conversion Fault
CCF5
RAM Fault
CCF6
CPU disturbance
PCE
Parameters copy Error
HE
Hall current detection fault
DE
Fault categories
CUE
Fault categories
PE.05 Running status at last fault
Setting range: 0~3 [StP]
0: StP Stop
1: Acc Accelerate