Chapter 2 Installation and Wiring
15
The longer the distance between the inverter and the motor, the higher the carrier frequency would be, and the
greater the high harmonic leakage current of the cables would be. Leakage current has a negative impact to inverters
and Equipment nearby, so reduce leakage current as little as possible.
The relationship of the distance between the inverter and the motor and carrier frequency is shown as Table 2-7
Table 2-7 Distance between the inverter and the motor and carrier frequency.
Distance between inverter and motor
Below 50m
Below 100m
Above 100m
Carrier frequency
Below 8 kHz
Below 4 kHz
Below 2 kHz