Chapter 5 Detailed Function Introductions
120
图 2
F/R
RUN
COM
图 1
REV
FWD
COM
图 4
F/R
HLD
COM
RUN
SB1
SB2
K
图 3
HLD
REV
COM
FWD
SB1
SB2
SB3
P3.16 Terminal UP/DN rate
Setting range: 0.01~99.99Hz/s [1.00Hz/s]
P3.17 UP/DN reference amplitude
Setting range:0.00~Frequency upper limit [10.00Hz]
Notes:
Terminal UP/DN rate is used to define the change rate of reference frequency that is changed by terminal
UP/DN. UP/DN reference amplitude used to define that the span of reference frequency is changed by
terminal UP/DN.
3.18 Digital frequency UP/DOWN save selection
Setting range: 0~2 [2]
0: Receive STOP, UP/DN reference is reset to zero;
1: Receive STOP, UP/DN reference is not reset to zero, and not saved when power loss;
2: UP / DOWN set point not is reset to 0 after receiving STOP, which will save to function code after power off;
when P0.03 is set to 1, P0.02 adjusts power-off saving online.
Notes:
UP / DOWN operation is shown in Fig. 5-3-3,5-3-4.
When P0.03 is set to 1 during the keypad setting frequency: When P3.18 is set to 2, the digital set frequency
(P0.02) adjusts the power-off saving; when P3.18 is not set to 2, it will not be saved after power failure,
please see P0. 02 description for details.
P3.19 D0 terminal function definitions
Setting range: 0 ~ thirty-five [ 0]
P3.20 Y1 terminal function definition (reserve for 3004GB and
below models)
Setting range: 0 ~ thirty-five [ 1]
P3.21 Y2 terminal function definition (reserve for 3004GB and
below models)
Setting range: 0 ~ thirty-five [ 0]
P3.22 Y3 terminal function definition (reserve for 3004GB and
below models)
Setting range: 0 ~ thirty-five [ 0]
P3.23 Y4 terminal function definition (reserve)
Setting range: 0 ~ thirty-five [ 0]
P3.24 relay 1 (TA / TB / TC) output function selection
Setting range: 0 ~ thirty-five [ nineteen]
P3.25 relay 2 (BRA / BRB / BRC) output function selection
(reserve for 3004GB and below models)
Setting range: 0 ~ thirty-five [ 0]
Fig. 1
Fig. 3
Fig. 4
Fig. 2