Chapter 4 Parameter Index
50
Functi
on code
Parameter
LCD display
Setting range
Factory
setting
Mod.
MODB
US
address
P0.10
Maximum output
frequency
Maximum
frequency
3004GB and below:
MAX [50.00Hz, upper limit
frequency, set frequency,
multi-stage frequency, jumping
frequency] ~ 650.0Hz
35R5GB and above:
MAX [50.00Hz, upper limit
frequency, set frequency,
multi-stage frequency, jumping
frequency] ~ 400.0Hz
50.00Hz
×
010A
P0.11
Upper limit
frequency source
Upper limit
frequency source
0: Digital setting
1: Terminal AI1
2: Terminal AI2
3: Terminal AI3 (reserve for
3004GB and below models)
4: Pulse input
5: Communication setting
0
×
010B
P0.12
Upper limit
frequency
Upper limit
frequency
MAX [lower limit frequency,
jog frequency, UP/DN given
amplitude, sleep threshold] ~
maximum frequency
50.00Hz
○
010C
P0.13
Offset of upper
limit frequency
Offset of upper
limit frequency
0.00Hz~upper limit frequency
0.00Hz
○
010D
P0.14
Rated voltage of
motor
Rated voltage of
motor
60~480V
Rated
voltage
*
010E
P0.15
Lower frequency
limit
Lower frequency
limit
0.00Hz~upper limit frequency
0.00Hz
○
010F
P0.16
Maximum output
voltage
Maximum output
voltage
60~480V
Rated
voltage
×
0110
P0.17
Knob adjusting
rate
Knob adjusting
rate
0: Digital knob integral
regulation
(1~250)
×
(0.01Hz/1rpm)
Knob adjusting rate
50
×
0111
P0.18
Acceleration
time 1
Acceleration
time 1
Power ≤ 132kW
0.1~3600s
Power ≥ 160kW
1.0~3600s
22kW
and
below:
6.0s
Others:
20.0s
○
0112
P0.19
Deceleration
time 1
Deceleration
time 1
Power ≤ 132kW
0.1~3600s
Power ≥ 160kW
1.0~3600s
22kW
and
below:
6.0s
Others:
20.0s
○
0113
Содержание 6000S series