Chapter 4 Parameter Index
74
P7: PID control
Functi
on
code
Parameter
name
LCD display
Setting range
Factory
setting
Mo
difi
cati
on
MOD
BUS
addres
s
P7.00
PID setting
source 1
PID setting
source 1
0: PID digital setting
1: AI1 terminal
2: AI2 terminal
3: Terminal AI3 (reserve for
3004GB and below models)
4: Pulse input
5: Serial communication
0
×
0800
P7.01
PID setting
source 2
PID setting
source 2
0~ 5: ditto.
0
×
0801
P7.02
Combination of
fixed variables
Combination
of fixed
variables
0: PID setting source 1
1: PID setting source 2
2: Min (PID setting source 1, PID
setting source 2)
3: Max (PID setting source 1, PID
setting source 2)
4: PID setting source 1 + PID
setting source 2
5: PID setting source 1 - PID
setting source 2
6: PID setting source 1 x PID
setting source 2
7: PID setting source 1 ÷ PID
setting source 2
0
×
0802
P7.03
PID feedback
source 1
PID feedback
source 1
0: Built-in PG or single-phase
speed measurement input
1: AI1 terminal
2: AI2 terminal
3: Terminal AI3 (reserve for
3004GB and below models)
4: Pulse input
5: Serial communication
0
×
0803
P7.04
PID feedback
source 2
PID feedback
source 2
0: Extended PG card speed
measurement input
1~ 5: ditto.
0
×
0804
P7.05
Combination of
feedback
quantity
Combination
of feedback
quantity
0: PID feedback source 1
1: PID feedback source 2
2: MIN (PID feedback source 1,
PID feedback source 2)
3: MAX (PID feedback source 1,
PID feedback source 2)
4: PID feedback source 1 + PID
feedback source 2
5: PID feedback source 1-PID
feedback source 2
0
×
0805
P7.06
Analog PID
digital setting
Analog PID
digital setting
-1000.0-1000.0, subject to
limitation of setting range
0.0
○
0806