Chapter 5 Detailed Function Introductions
100
Running Freq.(Hz)
Time
Acc Time
Dec Time
③
②
①
①
③
②
Figure.5-1-6 S-curve acceleration/deceleration
P1.08 Time of S-curve initial
Setting range: 10.0~50.0% [20.0%]
P1.09 Time of S-curve rising
Setting range: 10.0~80.0% [60.0%]
Notes:
P1.08 and P1.09 are only active when the Acc/Dec mode is S-curve mode (P1.07=1) and P1.08+P1.09
≤
90%.
Starting process of S-curve is shown in Figure. 5-1-6 as “
①
”, where the changing rate of output frequency
increases from 0.
Rising process of S-curve is shown in Figure. 5-1-6 as “
②
”, where the changing rate of output frequency is
constant.
Ending process of S-curve is shown in Figure. 5-1-6 as “
③
”, where the changing rate of output frequency
decreases to zero.
Tips:
S-curve Acc/Dec mode is suitable for the conveying load such as elevator and conveying belt.
P1.10 Stop mode
Setting range: 0~2 [0]
0: Deceleration to stop
1: Coast to stop
2: DeceleDC braking
Notes:
0: Dec-to-stop
After receiving the stop command, the inverter reduces its output frequency within the Dec time, and stops
when the frequency decreases to zero.
1: Coast-to-stop
After receiving the stop command, the inverter stops output immediately and the load stops under the effects
of mechanical inertia.
2: Dec-to-stop +DC braking
After receiving the stop command, the inverter reduces its output frequency according to the Dec time and
starts DC braking when its output frequency reaches the preset frequency of braking. Refer to the Notes of
P1.11~P1.15 for the functions of DC braking.