kzone1 sr
R
al
alreq
ct
L
2
pr
r
I
I
S
E
E
k R
R
I
I
×
æ
ö
³
=
× ×
+
+
ç
÷
è
ø
EQUATION1081 V2 EN-US
(Equation 540)
where:
I
kmax
Maximum primary fundamental frequency current for close-in forward and
reverse faults (A)
I
kzone1
Maximum primary fundamental frequency current for faults at the end of zone 1
reach (A)
I
pr
The rated primary CT current (A)
I
sr
The rated secondary CT current (A)
I
r
The rated current of the protection IED (A)
R
ct
The secondary resistance of the CT (
W
)
R
L
The resistance of the secondary wire and additional load (
W
). In solidly earthed
systems the loop resistance containing the phase and neutral wires should be
used for phase-to-earth faults and the resistance of the phase wire should be
used for three-phase faults.
In isolated or high impedance earthed systems the resistance of the single
secondary wire can always be used.
S
R
The burden of an IED current input channel (VA). S
R
=0.020 VA/channel for I
r
=1
A and S
R
=0.150 VA/channel for I
r
=5 A
a
This factor depends on the design of the protection function and can be a
function of the primary DC time constant of the close-in fault current.
k
This factor depends on the design of the protection function and can be a
function of the primary DC time constant of the fault current for a fault at the set
reach of zone 1.
The a- and k-factors have the following values for the different types of distance
function:
High speed distance: (ZMFPDIS and ZMFCPDIS)
Quadrilateral characteristic:
a = 1 for primary time constant Tp
£
400 ms
k = 3 for primary time constant Tp
£
200 ms
Mho characteristic:
a = 2 for primary time constant Tp
£
400 ms (For a = 1 the delay in operation
due to saturation is still under 1.5 cycles)
k = 3 for primary time constant Tp
£
200 ms
Quadrilateral distance: (ZMQPDIS, ZMQAPDIS and ZMCPDIS, ZMCAPDIS and
ZMMPDIS, ZMMAPDIS)
a = 1 for primary time constant Tp
£
100 ms
a = 3 for primary time constant Tp
>
100 and
£
400 ms
k = 4 for primary time constant Tp
£
50 ms
k = 5 for primary time constant Tp
>
50 and
£
150 ms
Mho distance: (ZMHPDIS)
a = 1 for primary time constant Tp
£
100 ms
a = 3 for primary time constant Tp
>
100 and
£
400 ms
k = 4 for primary time constant Tp
£
40 ms
k = 5 for primary time constant Tp
>
40 and
£
150 ms
1MRK 506 369-UEN B
Section 25
Requirements
Line distance protection REL670 2.2 IEC
883
Application manual
Содержание REL670 2.2 IEC
Страница 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Страница 2: ......
Страница 32: ...26 ...
Страница 70: ...64 ...
Страница 110: ...104 ...
Страница 152: ...146 ...
Страница 564: ...558 ...
Страница 570: ...564 ...
Страница 592: ...586 ...
Страница 706: ...700 ...
Страница 804: ...798 ...
Страница 848: ...842 ...
Страница 860: ...854 ...
Страница 882: ...876 ...
Страница 896: ...890 ...
Страница 906: ...900 ...
Страница 907: ...901 ...