Power flow
(MW)
(T.L.)
(S.C.)
(T.L. + S.C.)
Transmission
Line
Series
Compensation
500 kV
500 km
k = 50 %
en06000589.vsd
IEC06000589 V1 EN-US
Figure 70:
Self-regulating effect of reactive power balance
Increase in power transfer
SEMOD168320-45 v2
The increase in power transfer capability as a function of the degree of
compensation for a transmission line can be explained by studying the circuit
shown in figure
. The power transfer on the transmission line is given by the
( )
( )
(
)
sin
sin
1
d
d
×
×
×
×
=
=
-
× -
A
B
A
B
Line
C
Line
C
U
U
U
U
P
X
X
X
K
EQUATION1897 V1 EN-US
(Equation 47)
The compensation degree K
c
A
B
-jX
C
P
A
Q
A
P
B
Q
B
U
A
U
B
U
+jX
L
U
A
U
B
d
D
en06000590.vsd
IEC06000590 V1 EN-US
Figure 71:
Transmission line with series capacitor
The effect on the power transfer when considering a constant angle difference (δ)
between the line ends is illustrated in figure
. Practical compensation degree runs
from 20 to 70 percent. Transmission capability increases of more than two times
can be obtained in practice.
1MRK 506 369-UEN B
Section 8
Impedance protection
Line distance protection REL670 2.2 IEC
165
Application manual
Содержание REL670 2.2 IEC
Страница 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Страница 2: ......
Страница 32: ...26 ...
Страница 70: ...64 ...
Страница 110: ...104 ...
Страница 152: ...146 ...
Страница 564: ...558 ...
Страница 570: ...564 ...
Страница 592: ...586 ...
Страница 706: ...700 ...
Страница 804: ...798 ...
Страница 848: ...842 ...
Страница 860: ...854 ...
Страница 882: ...876 ...
Страница 896: ...890 ...
Страница 906: ...900 ...
Страница 907: ...901 ...