15.4.4
Interlocking for transformer bay AB_TRAFO
IP14149-1 v2
15.4.4.1
Application
M13567-3 v7
The interlocking for transformer bay (AB_TRAFO) function is used for a
transformer bay connected to a double busbar arrangement according to figure
The function is used when there is no disconnector between circuit breaker and
transformer. Otherwise, the interlocking for line bay (ABC_LINE) function can be
used. This function can also be used in single busbar arrangements.
QB1
QB2
QC1
QA1
QC2
WA1 (A)
WA2 (B)
QA2
QC3
T
QC4
QB4
QB3
QA2 and QC4 are not
used in this interlocking
AB_TRAFO
en04000515.vsd
IEC04000515 V1 EN-US
Figure 332:
Switchyard layout AB_TRAFO
M13566-4 v4
The signals from other bays connected to the module AB_TRAFO are described
below.
1MRK 506 369-UEN B
Section 15
Control
Line distance protection REL670 2.2 IEC
669
Application manual
Содержание REL670 2.2 IEC
Страница 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Страница 2: ......
Страница 32: ...26 ...
Страница 70: ...64 ...
Страница 110: ...104 ...
Страница 152: ...146 ...
Страница 564: ...558 ...
Страница 570: ...564 ...
Страница 592: ...586 ...
Страница 706: ...700 ...
Страница 804: ...798 ...
Страница 848: ...842 ...
Страница 860: ...854 ...
Страница 882: ...876 ...
Страница 896: ...890 ...
Страница 906: ...900 ...
Страница 907: ...901 ...