![ABB REL670 2.2 IEC Скачать руководство пользователя страница 310](http://html.mh-extra.com/html/abb/rel670-2-2-iec/rel670-2-2-iec_applications-manual_4789310.webp)
8.9.2.7
Tapped line application
GUID-1230B60C-8C3C-4405-8209-E089CAF07847 v1
C
B
BC
IEC09000160-3-en.vsd
A
IEC09000160 V3 EN-US
Figure 156:
Example of tapped line with Auto transformer.
This application gives rise to similar problem that was highlighted in section
, that is increased measured impedance due to fault
current infeed. For example, for faults between the T point and B station the
measured impedance at A and C will be
Z
A
=Z
AT
+ ·Z
TF
I
A
+ I
C
I
A
DOCUMENT11524-IMG3509 V3 EN-US
(Equation 246)
Z
Z
Z
I
I
I
Z
U
U
C
Trf
CT
A
C
C
TF
=
+
+
+
⋅
⋅
2
1
2
DOCUMENT11524-IMG3510 V3 EN-US
(Equation 247)
Where:
Z
AT
and Z
CT
is the line impedance from the A respective C station to the T point.
I
A
and I
C
is fault current from A respective C station for fault between T and B.
U2/U1
Transformation ratio for transformation of impedance at U1 side of the transformer to
the measuring side U2 (it is assumed that current and voltage distance function is
taken from U2 side of the transformer).
Z
TF
is the line impedance from the T point to the fault (F).
Z
Trf
Transformer impedance
Section 8
1MRK 506 369-UEN B
Impedance protection
304
Line distance protection REL670 2.2 IEC
Application manual
Содержание REL670 2.2 IEC
Страница 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Страница 2: ......
Страница 32: ...26 ...
Страница 70: ...64 ...
Страница 110: ...104 ...
Страница 152: ...146 ...
Страница 564: ...558 ...
Страница 570: ...564 ...
Страница 592: ...586 ...
Страница 706: ...700 ...
Страница 804: ...798 ...
Страница 848: ...842 ...
Страница 860: ...854 ...
Страница 882: ...876 ...
Страница 896: ...890 ...
Страница 906: ...900 ...
Страница 907: ...901 ...