ph ph
U
UBase
-
=
EQUATION2268 V1 EN-US
(Equation 535)
3U0>
: Level of high zero sequence voltage detection given in % of
UBase
. This
setting should be based on fault calculations to find the zero sequence voltage in
case of a fault at the most remote point where the direct trip scheme shall be active.
The zero sequence voltages shall be calculated for different types of earth faults
(single phase to earth and phase to phase to earth short circuits) at different
switching states in the network.
t3U0
: Time delay for trip in case of high zero sequence voltage detection. The trip
function can be used as stand alone earth fault protection with a long time delay.
The choice of time delay is depending on the application of the protection as well
as network topology.
16.8.9
Negative sequence overcurrent protection LCNSPTOC
GUID-0593B07A-4F76-4F92-92E9-EB30FC836ABE v1
16.8.9.1
Identification
GUID-EDC20AC7-540D-43DE-8ABF-7A463E115950 v1
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Negative sequence overcurrent
protection
LCNSPTOC
-
46
16.8.9.2
Application
GUID-D47B89E9-2279-4057-B77D-F27CDF84F1CE v1
Negative sequence symmetrical components are present in all types of fault
condition.
Negative sequence overcurrent protection (LCNSPTOC) is a definite time stage
comparator function. The negative sequence input current from the SMAI block is
connected as input to the function through a group connection I3P in PCM600.
This current is compared against the preset value and a start signal will be set high
if the input negative sequence current is greater than the preset value
I2>
. Trip
signal will be set high after a time delay setting of
tI2
. BLOCK input will block the
complete function. BLKTR will block the trip output. Negative sequence current is
available as service value output I2.
16.8.9.3
Setting guideline
GUID-377FEADE-375F-4B2D-ADDE-D92C59BDBD41 v2
GlobalBaseSel
: Selects the global base value group used by the function to define
IBase
,
UBase
and
SBase
as applicable.
1MRK 506 369-UEN B
Section 16
Scheme communication
Line distance protection REL670 2.2 IEC
737
Application manual
Содержание REL670 2.2 IEC
Страница 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Страница 2: ......
Страница 32: ...26 ...
Страница 70: ...64 ...
Страница 110: ...104 ...
Страница 152: ...146 ...
Страница 564: ...558 ...
Страница 570: ...564 ...
Страница 592: ...586 ...
Страница 706: ...700 ...
Страница 804: ...798 ...
Страница 848: ...842 ...
Страница 860: ...854 ...
Страница 882: ...876 ...
Страница 896: ...890 ...
Страница 906: ...900 ...
Страница 907: ...901 ...