![ABB REL670 2.2 IEC Скачать руководство пользователя страница 853](http://html.mh-extra.com/html/abb/rel670-2-2-iec/rel670-2-2-iec_applications-manual_4789853.webp)
Using
Echo
in this case is safe only if there is no risk of varying
transmission asymmetry.
GPSSyncErr
: when GPS synchronization is lost, synchronization of the line
differential function continues for 16 s based on the stability in the local IED
clocks. After that, setting
Block
blocks the line differential function or setting
Echo
keeps it on by using the
Echo
synchronization method.
Using
Echo
in this case is safe only if there is no risk of varying
transmission asymmetry.
CommSync
defines the
Master
and
Slave
relation in the communication system,
and should not be mistaken for the synchronization of line differential current
samples. When direct fiber is used, one LDCM is set as
Master
and the other as
Slave
. When a modem and multiplexer is used, the IED is always set as
Slave
because the telecommunication system provides the clock master.
OptoPower
has two settings:
LowPower
and
HighPower
.
Short-range LDCM: Use
LowPower
for fibres 0 – 1 km and
HighPower
for fibers
greater than 1 km.
Medium-range LDCM: Typical distance 80 km for both
LowPower
and
HighPower
.
Long-range LDCM: Typical distance 120 km for both
LowPower
and
HighPower
.
An optical budget calculation should be made for the actual case. For medium
range LDCM and long range LDCM the recommendation is to use the
LowPower
setting to minimize the power consumption and keep the heat dissipation at
minimum.
The
HighPower
setting adds 3 dBm extra optical power and can be used to increase
the margin at distances close to maximum.
Table 62:
Optical budgets with C37.94 protocol
Type of LDCM
Short range (SR)
Short range (SR)
Medium range
(MR)
Long range (LR)
Type of fibre
Multi-mode fiber
glass 50/125 μm
Multi-mode fiber
glass 62.5/125
μm
Single-mode fiber
glass 9/125 μm
Single-mode fiber
glass 9/125 μm
Modem type
1MRK0002122-
AB
1MRK0002122-
AB
1MRK002311-AA
1MRK002311-BA
Contact type
ST
ST
FC/PC
FC/PC
Table continues on next page
1MRK 506 369-UEN B
Section 22
Remote communication
Line distance protection REL670 2.2 IEC
847
Application manual
Содержание REL670 2.2 IEC
Страница 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Страница 2: ......
Страница 32: ...26 ...
Страница 70: ...64 ...
Страница 110: ...104 ...
Страница 152: ...146 ...
Страница 564: ...558 ...
Страница 570: ...564 ...
Страница 592: ...586 ...
Страница 706: ...700 ...
Страница 804: ...798 ...
Страница 848: ...842 ...
Страница 860: ...854 ...
Страница 882: ...876 ...
Страница 896: ...890 ...
Страница 906: ...900 ...
Страница 907: ...901 ...