14.3.2
Application
GUID-AD63BF6C-0351-4E48-9FB2-9AB5CF0C521E v2
Some protection functions operate on the basis of measured voltage at the relay
point. Examples of such protection functions are distance protection function,
undervoltage function and energisation-check function. These functions might mal-
operate if there is an incorrect measured voltage due to fuse failure or other kind of
faults in voltage measurement circuit.
VDSPVC is designed to detect fuse failures or faults in voltage measurement
circuit based on comparison of the voltages of the main and pilot fused circuits
phase wise. VDSPVC output can be configured to block voltage dependent
protection functions such as high-speed distance protection, undervoltage relays,
underimpedance relays and so on.
FuseFailSupvn
IED
L1
L2
L3
U
2
L1
U
2
L2
U
2
L3
U
1
L
1
U
1
L
2
U
1
L
3
IEC12000143-1-en.vsd
Main Vt circuit
P
ilo
t
V
T
c
ir
cu
it
IEC12000143 V1 EN-US
Figure 295:
Application of VDSPVC
1MRK 506 369-UEN B
Section 14
Secondary system supervision
Line distance protection REL670 2.2 IEC
593
Application manual
Содержание REL670 2.2 IEC
Страница 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Страница 2: ......
Страница 32: ...26 ...
Страница 70: ...64 ...
Страница 110: ...104 ...
Страница 152: ...146 ...
Страница 564: ...558 ...
Страница 570: ...564 ...
Страница 592: ...586 ...
Страница 706: ...700 ...
Страница 804: ...798 ...
Страница 848: ...842 ...
Страница 860: ...854 ...
Страница 882: ...876 ...
Страница 896: ...890 ...
Страница 906: ...900 ...
Страница 907: ...901 ...