These signals from each bus-coupler bay (ABC_BC) are needed:
Signal
BC12CLTR
A bus-coupler connection through the own bus-coupler exists between busbar WA1
and WA2.
BC17OPTR
No bus-coupler connection through the own bus-coupler between busbar WA1 and
WA7.
BC17CLTR
A bus-coupler connection through the own bus-coupler exists between busbar WA1
and WA7.
BC27OPTR
No bus-coupler connection through the own bus-coupler between busbar WA2 and
WA7.
BC27CLTR
A bus-coupler connection through the own bus-coupler exists between busbar WA2
and WA7.
VPBC12TR
The switch status of BC_12 is valid.
VPBC17TR
The switch status of BC_17 is valid.
VPBC27TR
The switch status of BC_27 is valid.
EXDU_BC
No transmission error from the bay that contains the above information.
These signals from each bus-section disconnector bay (A1A2_DC) are also needed.
For B1B2_DC, corresponding signals from busbar B are used. The same type of
module (A1A2_DC) is used for different busbars, that is, for both bus-section
disconnector A1A2_DC and B1B2_DC.
Signal
DCOPTR
The bus-section disconnector is open.
DCCLTR
The bus-section disconnector is closed.
VPDCTR
The switch status of bus-section disconnector DC is valid.
EXDU_DC
No transmission error from the bay that contains the above information.
If the busbar is divided by bus-section circuit breakers, the signals from the bus-
section coupler bay (A1A2_BS), rather than the bus-section disconnector bay
(A1A2_DC) must be used. For B1B2_BS, corresponding signals from busbar B are
used. The same type of module (A1A2_BS) is used for different busbars, that is,
for both bus-section circuit breakers A1A2_BS and B1B2_BS.
Signal
S1S2OPTR
No bus-section coupler connection between bus-sections 1 and 2.
S1S2CLTR
A bus-section coupler connection exists between bus-sections 1 and 2.
VPS1S2TR
The switch status of bus-section coupler BS is valid.
EXDU_BS
No transmission error from the bay that contains the above information.
For a line bay in section 1, these conditions are valid:
1MRK 506 369-UEN B
Section 15
Control
Line distance protection REL670 2.2 IEC
661
Application manual
Содержание REL670 2.2 IEC
Страница 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Страница 2: ......
Страница 32: ...26 ...
Страница 70: ...64 ...
Страница 110: ...104 ...
Страница 152: ...146 ...
Страница 564: ...558 ...
Страница 570: ...564 ...
Страница 592: ...586 ...
Страница 706: ...700 ...
Страница 804: ...798 ...
Страница 848: ...842 ...
Страница 860: ...854 ...
Страница 882: ...876 ...
Страница 896: ...890 ...
Страница 906: ...900 ...
Страница 907: ...901 ...