The extent of the oscillations depends on the extent of the disturbances and on the
natural stability of the system.
The oscillation rate depends also on the inertia of the system and on the total
system impedance between different generating units. These oscillations cause
changes in phase and amplitude of the voltage difference between the oscillating
generating units in the power system, which reflects further on in oscillating power
flow between two parts of the system - the power swings from one part to another -
and vice versa.
Distance IEDs located in interconnected networks see these power swings as the
swinging of the measured impedance in relay points. The measured impedance
varies with time along a locus in an impedance plane, see figure
. This locus
can enter the operating characteristic of a distance protection and cause, if no
preventive measures have been considered, its unwanted operation.
R
jX
Operating characteristic
Impedance locus at
power swing
IEC09000224_1_en.vsd
IEC09000224 V1 EN-US
Figure 223:
Impedance plane with Power swing detection operating
characteristic and impedance locus at power swing
8.14.2.2
Basic characteristics
M13874-11 v6
Power swing detection function (ZMRPSB) reliably detects power swings with
periodic time of swinging as low as 200 ms (which means slip frequency as high as
10% of the rated frequency on the 50 Hz basis). It detects the swings under normal
system operation conditions as well as during the dead time of a single-pole
automatic reclosing cycle.
ZMRPSB function is able to secure selective operation for internal faults during
power swing. The operation of the distance protection function remains stable for
external faults during the power swing condition, even with the swing (electrical)
centre located on the protected power line.
The operating characteristic of the ZMRPSB function is easily adjustable to the
selected impedance operating characteristics of the corresponding controlled
distance protection zones as well as to the maximum possible load conditions of
the protected power lines. See the corresponding description in
“Technical
reference manual”
for the IEDs.
Section 8
1MRK 506 369-UEN B
Impedance protection
408
Line distance protection REL670 2.2 IEC
Application manual
Содержание REL670 2.2 IEC
Страница 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Страница 2: ......
Страница 32: ...26 ...
Страница 70: ...64 ...
Страница 110: ...104 ...
Страница 152: ...146 ...
Страница 564: ...558 ...
Страница 570: ...564 ...
Страница 592: ...586 ...
Страница 706: ...700 ...
Страница 804: ...798 ...
Страница 848: ...842 ...
Страница 860: ...854 ...
Страница 882: ...876 ...
Страница 896: ...890 ...
Страница 906: ...900 ...
Страница 907: ...901 ...