tDuration
: The setting of the timer for the release of UILevel is, by default, 0.02
seconds, which has proven to be suitable in most cases from field experience. If a
shorter time delay is to be set, it is necessary to consider the voltage recovery time
during line energization.
tOperate
: The time delay for the
START_DLYD
input to activate
TRIP
when
Mode
is set to
Impedance
or
UILvl&Imp
is, by default, set to 0.03 seconds.
8.19
Phase preference logic PPLPHIZ
SEMOD151920-1 v2
8.19.1
Identification
SEMOD151937-2 v2
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Phase preference logic
PPLPHIZ
-
-
8.19.2
Application
SEMOD167856-4 v5
Phase preference logic function PPLPHIZ is an auxiliary function to Distance
protection zone, quadrilateral characteristic ZMQPDIS and Phase selection with
load encroachment, quadrilateral characteristic function FDPSPDIS. The purpose is
to create the logic in resonance or high resistive earthed systems (normally sub-
transmission) to achieve the correct phase selective tripping during two
simultaneous single-phase earth-faults in different phases on different line sections.
Due to the resonance/high resistive earthing principle, the earth faults in the system
gives very low fault currents, typically below 25 A. At the same time, the occurring
system voltages on the healthy phases will increase to line voltage level as the
neutral displacement is equal to the phase voltage level at a fully developed earth
fault. This increase of the healthy phase voltage, together with slow tripping, gives
a considerable increase of the risk of a second fault in a healthy phase and the
second fault can occur at any location. When it occurs on another feeder, the fault
is commonly called cross-country fault.
Different practices for tripping is used by different utilities. The main use of this
logic is in systems where single phase-to-earth faults are not automatically cleared,
only alarm is given and the fault is left on until a suitable time to send people to
track down and repair the fault. When cross-country faults occur, the practice is to
trip only one of the faulty lines. In other cases, a sensitive, directional earth-fault
protection is provided to trip, but due to the low fault currents long tripping times
are utilized.
Figure
shows an occurring cross-country fault. Figure
shows the
achievement of line voltage on healthy phases and an occurring cross-country fault.
1MRK 506 369-UEN B
Section 8
Impedance protection
Line distance protection REL670 2.2 IEC
445
Application manual
Содержание REL670 2.2 IEC
Страница 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Страница 2: ......
Страница 32: ...26 ...
Страница 70: ...64 ...
Страница 110: ...104 ...
Страница 152: ...146 ...
Страница 564: ...558 ...
Страница 570: ...564 ...
Страница 592: ...586 ...
Страница 706: ...700 ...
Страница 804: ...798 ...
Страница 848: ...842 ...
Страница 860: ...854 ...
Страница 882: ...876 ...
Страница 896: ...890 ...
Страница 906: ...900 ...
Страница 907: ...901 ...