IL3=IN
IL1=IN
en06000553.vsd
IEC06000553 V1 EN-US
Figure 244:
The currents in the phases at a double earth fault
The function has a block input (BLOCK) to block start from the function if
required in certain conditions.
8.19.3
Setting guidelines
SEMOD167997-4 v5
The parameters for the Phase preference logic function PPLPHIZ are set via the
local HMI or PCM600.
Phase preference logic function is an intermediate logic between
Distance protection zone, quadrilateral characteristic function
ZMQPDIS and Phase selection with load encroachment,
quadrilateral characteristic function FDPSPDIS. Phase selection
and zones are set according to normal praxis, including earth-fault
loops, although earth-fault loops will only be active during a cross-
country fault.
GlobalBaseSel
: Selects the global base value group used by the function to define
IBase
,
UBase
and
SBase
as applicable.
OperMode
: The operating mode is selected. Choices includes cyclic or acyclic
phase selection in the preferred mode. This setting must be identical for all IEDs in
the same galvanic connected network part.
UPN<
: The setting of the phase-to- earth voltage level (phase voltage) which is
used by the evaluation logic to verify that a fault exists in the phase. Normally in a
high impedance earthed system, the voltage drop is big and the setting can typically
be set to 70% of base voltage (
UBase
)
Section 8
1MRK 506 369-UEN B
Impedance protection
448
Line distance protection REL670 2.2 IEC
Application manual
Содержание REL670 2.2 IEC
Страница 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Страница 2: ......
Страница 32: ...26 ...
Страница 70: ...64 ...
Страница 110: ...104 ...
Страница 152: ...146 ...
Страница 564: ...558 ...
Страница 570: ...564 ...
Страница 592: ...586 ...
Страница 706: ...700 ...
Страница 804: ...798 ...
Страница 848: ...842 ...
Страница 860: ...854 ...
Страница 882: ...876 ...
Страница 896: ...890 ...
Страница 906: ...900 ...
Страница 907: ...901 ...