![ABB REL670 2.2 IEC Скачать руководство пользователя страница 554](http://html.mh-extra.com/html/abb/rel670-2-2-iec/rel670-2-2-iec_applications-manual_4789554.webp)
G
U/f>
24
U/f>
24
U/f>
24
en05000208.vsd
IEC05000208 V1 EN-US
Figure 289:
Alternative connections of an Overexcitation protection
OEXPVPH(Volt/Hertz)
10.4.3
Setting guidelines
IP15039-1 v1
10.4.3.1
Recommendations for input and output signals
M6496-75 v4
Recommendations for Input signals
M6496-79 v5
Please see the default factory configuration.
BLOCK
: The input will block the operation of the Overexcitation protection
OEXPVPH, for example, the block input can be used to block the operation for a
limited time during special service conditions.
RESET
: OEXPVPH has a thermal memory, which can take a long time to reset.
Activation of the RESET input will reset the function instantaneously.
Recommendations for Output signals
M6496-84 v7
Please see the default factory configuration for examples of configuration.
ERROR
: The output indicates a measuring error. The reason, for example, can be
configuration problems where analogue signals are missing.
START
: The START output indicates that the level V/Hz>> has been reached. It
can be used to initiate time measurement.
TRIP
: The TRIP output is activated after the operate time for the U/f level has
expired. TRIP signal is used to trip the circuit breaker(s).
Section 10
1MRK 506 369-UEN B
Voltage protection
548
Line distance protection REL670 2.2 IEC
Application manual
Содержание REL670 2.2 IEC
Страница 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Страница 2: ......
Страница 32: ...26 ...
Страница 70: ...64 ...
Страница 110: ...104 ...
Страница 152: ...146 ...
Страница 564: ...558 ...
Страница 570: ...564 ...
Страница 592: ...586 ...
Страница 706: ...700 ...
Страница 804: ...798 ...
Страница 848: ...842 ...
Страница 860: ...854 ...
Страница 882: ...876 ...
Страница 896: ...890 ...
Страница 906: ...900 ...
Страница 907: ...901 ...