ALARM
: The output is activated when the alarm level has been reached and the
alarm timer has elapsed. When the system voltage is high this output sends an
alarm to the operator.
10.4.3.2
Settings
M6496-91 v7
GlobalBaseSel
: Selects the global base value group used by the function to define
IBase
,
UBase
and
SBase
as applicable.
Operation
: The operation of the Overexcitation protection OEXPVPH can be set to
On
/
Off
.
MeasuredU
: The phases involved in the measurement are set here. Normally the
three phase measurement measuring the positive sequence voltage should be used
but when only individual VT's are used a single phase-to-phase can be used.
MeasuredI:
The phases involved in the measurement are set here.
MeasuredI:
must
be in accordance with
MeasuredU
.
V/Hz>
: Operating level for the inverse characteristic, IEEE or tailor made. The
operation is based on the relation between rated voltage and rated frequency and
set as a percentage factor. Normal setting is around 108-110% depending of the
capability curve for the transformer/generator.
V/Hz>>
: Operating level for the
tMin
definite time delay used at high
overvoltages. The operation is based on the relation between rated voltage and
rated frequency and set as a percentage factor. Normal setting is around 110-180%
depending of the capability curve of the transformer/generator. Setting should be
above the knee-point when the characteristic starts to be straight on the high side.
XLeak
: The transformer leakage reactance on which the compensation of voltage
measurement with load current is based. The setting shall be the transformer leak
reactance in primary ohms. If no current compensation is used (mostly the case) the
setting is not used.
TrPulse
: The length of the trip pulse. Normally the final trip pulse is decided by the
trip function block. A typical pulse length can be 50 ms.
CurveType
: Selection of the curve type for the inverse delay. The IEEE curves or
tailor made curve can be selected depending of which one matches the capability
curve best.
kForIEEE
: The time constant for the inverse characteristic. Select the one giving
the best match to the transformer capability.
tCooling
: The cooling time constant giving the reset time when voltages drops
below the set value. Shall be set above the cooling time constant of the transformer.
The default value is recommended to be used if the constant is not known.
tMin
: The operating times at voltages higher than the set
V/Hz>>
. The setting shall
match capabilities on these high voltages. Typical setting can be 1-10 second.
1MRK 506 369-UEN B
Section 10
Voltage protection
Line distance protection REL670 2.2 IEC
549
Application manual
Содержание REL670 2.2 IEC
Страница 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Страница 2: ......
Страница 32: ...26 ...
Страница 70: ...64 ...
Страница 110: ...104 ...
Страница 152: ...146 ...
Страница 564: ...558 ...
Страница 570: ...564 ...
Страница 592: ...586 ...
Страница 706: ...700 ...
Страница 804: ...798 ...
Страница 848: ...842 ...
Страница 860: ...854 ...
Страница 882: ...876 ...
Страница 896: ...890 ...
Страница 906: ...900 ...
Страница 907: ...901 ...