Using PTP for synchronizing the MU
SAM600 VT
SAM600 CT
SAM600 TS
IED
PTP
9-2
IEC17000040-1-en.vsdx
IEC17000040 V1 EN-US
Figure 412:
Setting example with PTP synchronization
Settings on the local HMI under
Main menu/Configuration/Time/
Synchronization/TIMESYNCHGEN:1/IEC61850-9-2
:
•
HwSyncSrc
: is not used as the SW-time and HW-time are connected with each
other due to PTP
•
SyncLostMode
: set to
Block
to block protection functions if time
synchronization is lost or set to
BlockOnLostUTC
if the protection functions
are to be blocked when global common synchronization is lost
•
SyncAccLevel
: can be set to
1μs
since this corresponds to a maximum phase
angle error of 0.018 degrees at 50Hz
Settings on the local HMI under
Main menu/Configuration/Communication/
Ethernet configuration/Access point/AP_X
:
•
Operation: On
•
PTP: On
1MRK 506 369-UEN B
Section 21
Station communication
Line distance protection REL670 2.2 IEC
823
Application manual
Содержание REL670 2.2 IEC
Страница 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Страница 2: ......
Страница 32: ...26 ...
Страница 70: ...64 ...
Страница 110: ...104 ...
Страница 152: ...146 ...
Страница 564: ...558 ...
Страница 570: ...564 ...
Страница 592: ...586 ...
Страница 706: ...700 ...
Страница 804: ...798 ...
Страница 848: ...842 ...
Страница 860: ...854 ...
Страница 882: ...876 ...
Страница 896: ...890 ...
Страница 906: ...900 ...
Страница 907: ...901 ...