Section 1
Section 2
A1A2_DC(BS)
B1B2_DC(BS)
BB_ES
BB_ES
BH_LINE
(WA1)A1
(WA2)B1
B2
A2
en04000512.vsd
BH_LINE
IEC04000512 V1 EN-US
Figure 358:
Busbars divided by bus-section disconnectors (circuit breakers)
The project-specific logic are the same as for the logic for the double busbar
configuration described in section “Signals in single breaker arrangement”.
Signal
BB_DC_OP
All disconnectors on this part of the busbar are open.
VP_BB_DC
The switch status of all disconnectors on this part of the busbar is valid.
EXDU_BB
No transmission error from any bay that contains the above information.
15.4.8
Interlocking for double CB bay DB
IP14167-1 v2
15.4.8.1
Application
M13585-3 v10
The interlocking for a double busbar double circuit breaker bay including
DB_BUS_A, DB_BUS_B and DB_LINE functions are used for a line connected to
a double busbar arrangement according to figure
Section 15
1MRK 506 369-UEN B
Control
688
Line distance protection REL670 2.2 IEC
Application manual