R
X
Distance measuring zone
Phase selection
”Quadrilateral” zone
(ohm/phase)
(ohm/phase)
en05000674.vsd
IEC05000674 V1 EN-US
Figure 161:
Operation characteristic for FRPSPDIS in forward direction for
three-phase fault, ohm/phase domain
The result from rotation of the load characteristic at a fault between two phases is
presented in fig
. Since the load characteristic is based on the same
measurement as the quadrilateral characteristic, it will rotate with the quadrilateral
characteristic clockwise by 30 degrees when subject to a pure phase-to-phase fault.
At the same time, the characteristic "shrinks" by 2/√3, from the full RLdFw/RLdRv
reach, which is valid at load or three-phase fault.
1MRK 506 369-UEN B
Section 8
Impedance protection
Line distance protection REL670 2.2 IEC
317
Application manual