Figure 253:
Directional function characteristic
1. RCA = Relay characteristic angle
2. ROA = Relay operating angle
3. Reverse
4. Forward
9.2.3.1
Settings for each step
M12982-19 v10
x
means step 1, 2, 3 and 4.
DirModex
: The directional mode of step
x
. Possible settings are
Off
/
Non-
directional
/
Forward
/
Reverse
.
Characteristx
: Selection of time characteristic for step
x
. Definite time delay and
different types of inverse time characteristics are available according to Table
1MRK 506 369-UEN B
Section 9
Current protection
Line distance protection REL670 2.2 IEC
463
Application manual