Figure 279:
Typical connection for STBPTOC in 1½-breaker arrangement.
9.9.3
Setting guidelines
M12909-3 v5
The parameters for Stub protection STBPTOC are set via the local HMI or
PCM600.
The following settings can be done for the stub protection.
GlobalBaseSel
: Selects the global base value group used by the function to define
IBase
,
UBase
and
SBase
as applicable.
Operation
:
Off
/
On
ReleaseMode
: This parameter can be set
Release
or
Continuous
. With the
Release
setting the function is only active when a binary release signal RELEASE into the
function is activated. This signal is normally taken from an auxiliary contact
(normally closed) of the line disconnector and connected to a binary input
RELEASE of the IED. With the setting
Continuous
the function is activated
independent of presence of any external release signal.
Section 9
1MRK 506 369-UEN B
Current protection
512
Line distance protection REL670 2.2 IEC
Application manual
Содержание REL670 2.2 IEC
Страница 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Страница 2: ......
Страница 32: ...26 ...
Страница 70: ...64 ...
Страница 110: ...104 ...
Страница 152: ...146 ...
Страница 564: ...558 ...
Страница 570: ...564 ...
Страница 592: ...586 ...
Страница 706: ...700 ...
Страница 804: ...798 ...
Страница 848: ...842 ...
Страница 860: ...854 ...
Страница 882: ...876 ...
Страница 896: ...890 ...
Страница 906: ...900 ...
Страница 907: ...901 ...