no voltage selection,
No voltage sel.
•
single circuit breaker with double bus,
Double bus
•
1 1/2 circuit breaker arrangement with the breaker connected to busbar 1,
1 1/2
bus CB
•
1 1/2 circuit breaker arrangement with the breaker connected to busbar 2,
1 1/2
bus alt. CB
•
1 1/2 circuit breaker arrangement with the breaker connected to line 1 and 2,
Tie CB
PhaseShift
This setting is used to compensate the phase shift between the measured bus
voltage and line voltage when:
•
different phase-neutral voltages are selected (for example UL1 for bus and
UL2 for line);
•
one available voltage is phase-phase and the other one is phase-neutral (for
example UL1L2 for bus and UL1 for line).
The set value is added to the measured line phase angle. The bus voltage is
reference voltage.
Synchronizing settings
OperationSynch
The setting
Off
disables the Synchronizing function. With the setting
On
, the
function is in the service mode and the output signal depends on the input
conditions.
UHighBusSynch
and
UHighLineSynch
The voltage level settings shall be chosen in relation to the bus/line network
voltage. The threshold voltages
UHighBusSynch
and
UHighLineSynch
have to be
set lower than the value where the network is expected to be synchronized. A
typical value is 80% of the rated voltage.
UDiffSynch
Setting of the voltage difference between the line voltage and the bus voltage. The
difference is set depending on the network configuration and expected voltages in
the two networks running asynchronously. A normal setting is 0.10-0.15 p.u.
FreqDiffMin
The setting
FreqDiffMin
is the minimum frequency difference where the systems
are defined to be asynchronous. For frequency differences lower than this value,
the systems are considered to be in parallel. A typical value for
FreqDiffMin
is 10
mHz. Generally, the value should be low if both synchronizing and synchrocheck
functions are provided, and it is better to let the synchronizing function close, as it
1MRK 506 369-UEN B
Section 15
Control
Line distance protection REL670 2.2 IEC
609
Application manual
Содержание REL670 2.2 IEC
Страница 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Страница 2: ......
Страница 32: ...26 ...
Страница 70: ...64 ...
Страница 110: ...104 ...
Страница 152: ...146 ...
Страница 564: ...558 ...
Страница 570: ...564 ...
Страница 592: ...586 ...
Страница 706: ...700 ...
Страница 804: ...798 ...
Страница 848: ...842 ...
Страница 860: ...854 ...
Страница 882: ...876 ...
Страница 896: ...890 ...
Страница 906: ...900 ...
Страница 907: ...901 ...