Settings
DFTRefExtOut
and
DFTReference
shall be set to default
value
InternalDFTRef
if no VT inputs are available.
Even if the user sets the
AnalogInputType
of a SMAI block to
“
Current
”, the
MinValFreqMeas
is still visible. However, using the
current channel values as base for frequency measurement is
not
recommendable
for a number of reasons, not last among them
being the low level of currents that one can have in normal
operating conditions.
Examples of adaptive frequency tracking
Preprocessing block shall only be used to feed functions within the
same execution cycles (e.g. use preprocessing block with cycle 1 to
feed transformer differential protection). The only exceptions are
measurement functions (CVMMXN, CMMXU,VMMXU, etc.)
which shall be fed by preprocessing blocks with cycle 8.
When two or more preprocessing blocks are used to feed one
protection function (e.g. over-power function GOPPDOP), it is of
outmost importance that parameter setting DFTReference has the
same set value for all of the preprocessing blocks involved
Section 24
1MRK 506 369-UEN B
Basic IED functions
864
Line distance protection REL670 2.2 IEC
Application manual
Содержание REL670 2.2 IEC
Страница 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Страница 2: ......
Страница 32: ...26 ...
Страница 70: ...64 ...
Страница 110: ...104 ...
Страница 152: ...146 ...
Страница 564: ...558 ...
Страница 570: ...564 ...
Страница 592: ...586 ...
Страница 706: ...700 ...
Страница 804: ...798 ...
Страница 848: ...842 ...
Страница 860: ...854 ...
Страница 882: ...876 ...
Страница 896: ...890 ...
Страница 906: ...900 ...
Страница 907: ...901 ...