The IED can also be provided with full bay control and interlocking functionality
including co-operation with the synchrocheck function to allow integration of the
main or back-up control.
Out of Step function is available to separate power system sections close to
electrical centre at occurring out of step.
The IED can be used in applications with IEC/UCA 61850-9-2LE process bus with
up to eight merging units (MU) depending on other functionality included in the
IED. Each MU has eight analogue channels, normally four currents and four
voltages. Conventional and Merging Unit channels can be mixed freely in the
application.
Logic is prepared with a graphical tool. The advanced logic capability allows
special applications such as automatic opening of disconnectors in multi-breaker
arrangements, closing of breaker rings, load transfer logics and so on. The
graphical configuration tool with delay mode, ensures simple and fast testing and
commissioning.
Disturbance recorder and fault locator are available to allow independent post-fault
analysis after primary disturbances.
Forcing of binary inputs and outputs is a convenient way to test wiring in
substations as well as testing configuration logic in the IEDs. Basically it means
that all binary inputs and outputs on the IED I/O modules (BOM, BIM, IOM &
SOM) can be forced to arbitrary values.
Central Account Management is an authentication infrastructure that offers a
secure solution for enforcing access control to IEDs and other systems within a
substation. This incorporates management of user accounts, roles and certificates
and the distribution of such, a procedure completely transparent to the user.
Flexible Product Naming allows the customer to use an IED-vendor independent
IEC 61850 model of the IED. This customer model will be used as the IEC 61850
data model, but all other aspects of the IED will remain unchanged (e.g., names on
the local HMI and names in the tools). This offers significant flexibility to adapt
the IED to the customers' system and standard solution.
M11788-3 v10
Communication via optical connections ensures immunity against disturbances.
GUID-F5776DD1-BD04-4872-BB89-A0412B4B5CC3 v1
The following tables list all the functions available in the IED.
Those functions that are not exposed to the user or do not need to
be configured are not described in this manual.
Section 2
1MRK 506 369-UEN B
Application
42
Line distance protection REL670 2.2 IEC
Application manual
Содержание REL670 2.2 IEC
Страница 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Страница 2: ......
Страница 32: ...26 ...
Страница 70: ...64 ...
Страница 110: ...104 ...
Страница 152: ...146 ...
Страница 564: ...558 ...
Страница 570: ...564 ...
Страница 592: ...586 ...
Страница 706: ...700 ...
Страница 804: ...798 ...
Страница 848: ...842 ...
Страница 860: ...854 ...
Страница 882: ...876 ...
Страница 896: ...890 ...
Страница 906: ...900 ...
Страница 907: ...901 ...