Minimum voltage U
min
and maximum current I
max
are related to the same
operating conditions. Minimum load impedance occurs normally under emergency
conditions.
As a safety margin is required to avoid load encroachment under
three-phase conditions and to guarantee correct healthy phase IED
operation under combined heavy three-phase load and earth faults,
consider both: phase-to-phase and phase-to-earth fault operating
characteristics.
To avoid load encroachment for the phase-to-earth measuring elements, the set
resistive reach of any distance protection zone must be less than 80% of the
minimum load impedance.
RFFwPE
Z
load
≤
⋅
0 8
.
IEC13000273 V1 EN-US
(Equation 142)
This equation is applicable only when the loop characteristic angle for the single
phase-to-earth faults is more than three times as large as the maximum expected
load-impedance angle. For the case when the loop characteristic angle is less than
three times the load-impedance angle, more accurate calculations are necessary
according to equation
.
RFFwPE
Z
R
R
X
X
load
≤
⋅
⋅
∂ −
⋅
+
⋅
+
⋅
∂
0 8
2
1
0
2
1
0
.
cos
sin
min
IEC13000274 V1 EN-US
(Equation 143)
Where:
∂
is a maximum load-impedance angle, related to the maximum load power.
To avoid load encroachment for the phase-to-phase measuring elements, the set
resistive reach of any distance protection zone must be less than 160% of the
minimum load impedance.
RFFwPE
Z
load
≤
⋅
1 6
.
IEC13000275 V1 EN-US
(Equation 144)
is applicable only when the loop characteristic angle for the phase-to-
phase faults is more than three times as large as the maximum expected load-
impedance angle. More accurate calculations are necessary according to
equation
.
1MRK 506 369-UEN B
Section 8
Impedance protection
Line distance protection REL670 2.2 IEC
231
Application manual
Содержание REL670 2.2 IEC
Страница 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Страница 2: ......
Страница 32: ...26 ...
Страница 70: ...64 ...
Страница 110: ...104 ...
Страница 152: ...146 ...
Страница 564: ...558 ...
Страница 570: ...564 ...
Страница 592: ...586 ...
Страница 706: ...700 ...
Страница 804: ...798 ...
Страница 848: ...842 ...
Страница 860: ...854 ...
Страница 882: ...876 ...
Страница 896: ...890 ...
Страница 906: ...900 ...
Страница 907: ...901 ...