All this is applicable for all measuring zones when no power swing detection
element is in the protection scheme. Use an additional safety margin of
approximately 20% in cases when a power swing detection element is in the
protection scheme, refer to the description of Power swing detection (ZMRPSB)
function.
8.1.3.9
Load impedance limitation, with load encroachment function
activated
SEMOD168247-129 v2
The parameters for load encroachment shaping of the characteristic are found in the
description of the phase selection with load encroachment function, section
. If the characteristic for the impedance measurement is shaped
with the load encroachment algorithm, the parameter
RLdFw
and the
corresponding load angle
ArgLd
must be set according to the minimum load
impedance.
8.1.3.10
Setting of minimum operating currents
SEMOD168247-132 v2
The operation of the distance function can be blocked if the magnitude of the
currents is below the set value of the parameter
IMinOpPP
and
IMinOpPE
.
The default setting of
IMinOpPP
and
IMinOpPE
is 20% of
IBase
where
IBase
is
the chosen base current for the analog input channels. The value has been proven in
practice to be suitable in most of the applications. However, there might be
applications where it is necessary to increase the sensitivity by reducing the
minimum operating current down to 10% of IED base current. This happens
especially in cases, when the IED serves as a remote back-up protection on series
of very long transmission lines.
If the load current compensation is activated, there is an additional criteria
IMinOpIN
that will block the phase-earth loop if the 3I0<
IMinOpIN
. The default
setting of
IMinOpIN
is 5% of the IED base current
IBase
.
The minimum operating fault current is automatically reduced to 75% of its set
value, if the distance protection zone has been set for the operation in reverse
direction.
8.1.3.11
Setting of timers for distance protection zones
SEMOD168247-138 v2
The required time delays for different distance-protection zones are independent of
each other. Distance protection zone1 can also have a time delay, if so required for
selectivity reasons. One can set the time delays for all zones (basic and optional) in
a range of 0 to 60 seconds. The tripping function of each particular zone can be
inhibited by setting the corresponding
Operation
parameter to
Off
. Different time
delays are possible for the ph-E (
tPE
) and for the ph-ph (
tPP
) measuring loops in
each distance protection zone separately, to further increase the total flexibility of a
distance protection.
1MRK 506 369-UEN B
Section 8
Impedance protection
Line distance protection REL670 2.2 IEC
201
Application manual
Содержание REL670 2.2 IEC
Страница 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Страница 2: ......
Страница 32: ...26 ...
Страница 70: ...64 ...
Страница 110: ...104 ...
Страница 152: ...146 ...
Страница 564: ...558 ...
Страница 570: ...564 ...
Страница 592: ...586 ...
Страница 706: ...700 ...
Страница 804: ...798 ...
Страница 848: ...842 ...
Страница 860: ...854 ...
Страница 882: ...876 ...
Страница 896: ...890 ...
Страница 906: ...900 ...
Страница 907: ...901 ...