importing power that might occur instead of maximum exporting power and the
relevant Umin voltage for this condition.
8.10.4.2
Minimum operate currents
GUID-5B4DF48C-48ED-433D-92D8-B146E8A8A7E0 v1
FRPSPDIS has two current setting parameters, which blocks the respective phase-
to-earth loop and phase-to-phase loop if the RMS value of the phase current (ILn)
and phase difference current (ILmILn) is below the settable threshold.
The threshold to activate the phase selector for phase-to-earth (
IMinOpPE
) is set to
the default value or a level to securely detect a single line-to-earth fault at the
furthest reach of the phase selection. It is recommended to set
IMinOpPP
to double
value of
IMinOpPE
.
The threshold for opening the measuring loop for phase-to-earth fault
(
INReleasePE
) is set securely detect single line-to-earth fault at remote end on the
protected line. It is recommended to set
INBlockPP
to double value of
INReleasePE
.
8.11
Phase selection, quad, fixed angle, load
encroachment FDPSPDIS
IP12400-1 v4
8.11.1
Identification
8.11.1.1
Identification
M14850-1 v6
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Phase selection, quad, fixed angle,
load encroachment
FDPSPDIS
Z<phs
SYMBOL-DD V1 EN-US
21
8.11.2
Application
M13138-3 v3
The operation of transmission networks today is in many cases close to the stability
limit. The ability to accurately and reliably classify the different types of fault, so
that single pole tripping and autoreclosing can be used plays an important role in
this matter. Phase selection with load encroachment function FDPSPDIS is
designed to accurately select the proper fault loop in the distance measuring
function depending on the fault type.
The heavy load transfer that is common in many transmission networks may in
some cases be in opposite to the wanted fault resistance coverage. Therefore, the
function has a built in algorithm for load encroachment, which gives the possibility
1MRK 506 369-UEN B
Section 8
Impedance protection
Line distance protection REL670 2.2 IEC
325
Application manual
Содержание REL670 2.2 IEC
Страница 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Страница 2: ......
Страница 32: ...26 ...
Страница 70: ...64 ...
Страница 110: ...104 ...
Страница 152: ...146 ...
Страница 564: ...558 ...
Страница 570: ...564 ...
Страница 592: ...586 ...
Страница 706: ...700 ...
Страница 804: ...798 ...
Страница 848: ...842 ...
Страница 860: ...854 ...
Страница 882: ...876 ...
Страница 896: ...890 ...
Страница 906: ...900 ...
Страница 907: ...901 ...