Operation
:
Off
/
On
FunctionMode
This parameter can be set
Current
or
Contact
. This states the way
the detection of failure of the breaker is performed. In the mode current the current
measurement is used for the detection. In the mode
Contact
the long duration of
breaker position signal is used as indicator of failure of the breaker. The mode
Current/Contact
means that both ways of detections are activated.
Contact
mode
can be usable in applications where the fault current through the circuit breaker is
small. This can be the case for some generator protection application (for example
reverse power protection) or in case of line ends with weak end infeed.
RetripMode
: This setting states how the re-trip function shall operate.
Retrip Off
means that the re-trip function is not activated.
CB Pos Check
(circuit breaker
position check) and
Current
means that a phase current must be larger than the
operate level to allow re-trip.
CB Pos Check
(circuit breaker position check) and
Contact
means re-trip is done when circuit breaker is closed (breaker position is
used).
No CBPos Check
means re-trip is done without any check of breaker
position.
Table 39:
Dependencies between parameters RetripMode and FunctionMode
RetripMode
FunctionMode
Description
Retrip Off
N/A
the re-trip function is not
activated
CB Pos Check
Current
re-trip is done if the phase
current is larger than the
operate level after re-trip time
has elapsed
Contact
re-trip is done when auxiliary
contact position indicates that
breaker is still closed after re-
trip time has elapsed
Current/Contact
both methods according to
above are used but taken into
account also
I>BlkCont
No CBPos Check
Current
re-trip is done without check of
current level
Contact
re-trip is done without check of
auxiliary contact position
Current/Contact
re-trip is done without check of
current level or auxiliary contact
position
BuTripMode
: Back-up trip mode is given to state sufficient current criteria to detect
failure to break. For
Current
operation
2 out of 4
means that at least two currents,
of the three-phase currents and the residual current, shall be high to indicate
breaker failure.
1 out of 3
means that at least one current of the three-phase currents
shall be high to indicate breaker failure.
1 out of 4
means that at least one current of
the three-phase currents or the residual current shall be high to indicate breaker
failure. In most applications
1 out of 3
is sufficient. For
Contact
operation means
back-up trip is done when circuit breaker is closed (breaker position is used).
Section 9
1MRK 506 369-UEN B
Current protection
508
Line distance protection REL670 2.2 IEC
Application manual
Содержание REL670 2.2 IEC
Страница 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Страница 2: ......
Страница 32: ...26 ...
Страница 70: ...64 ...
Страница 110: ...104 ...
Страница 152: ...146 ...
Страница 564: ...558 ...
Страница 570: ...564 ...
Страница 592: ...586 ...
Страница 706: ...700 ...
Страница 804: ...798 ...
Страница 848: ...842 ...
Страница 860: ...854 ...
Страница 882: ...876 ...
Страница 896: ...890 ...
Страница 906: ...900 ...
Страница 907: ...901 ...