4. Set
Characteristic
to
IEC Def. Time
.
5. Set
tDef_OC
to
6000.00
s, if no trip of the overcurrent stage is required.
6. Set
VDepFact
to the value
100
% in order to ensure that the start value of the
overcurrent stage is constant, irrespective of the magnitude of the generator
voltage.
7. Set
Operation_UV
to
On
to activate the undervoltage stage.
8. Set
StartVolt
to the values
70
%.
9. Set
tDef_UV
to
3.0
s.
10. Set
EnBlkLowV
to
Off
(default value) to disable the cut-off level for low-
voltage of the undervoltage stage.
The other parameters may be left at their default value.
Section 9
1MRK 506 369-UEN B
Current protection
532
Line distance protection REL670 2.2 IEC
Application manual