8.5.3
Setting guidelines
SEMOD154701-1 v1
8.5.3.1
General
SEMOD154704-4 v2
The settings for the Full-scheme distance protection, quadrilateral for earth faults
(ZMMPDIS) function are done in primary values. The instrument transformer ratio
that has been set for the analogue input card is used to automatically convert the
measured secondary input signals to primary values used in ZMMPDIS function.
The following basics should be considered, depending on application, when doing
the setting calculations:
•
Errors introduced by current and voltage instrument transformers, particularly
under transient conditions.
•
Inaccuracies in the line zero-sequence impedance data, and their effect on the
calculated value of the earth-return compensation factor.
•
The effect of infeed between the IED and the fault location, including the
influence of different Z0/Z1 ratios of the various sources.
•
The phase impedance of non transposed lines is not identical for all fault
loops. The difference between the impedances for different phase-to-earth
loops can be as large as 5-10% of the total line impedance.
•
The effect of a load transfer between the IEDs of the protected fault resistance
is considerable, the effect must be recognized.
•
Zero-sequence mutual coupling from parallel lines.
8.5.3.2
Setting of zone1
SEMOD154704-15 v1
The different errors mentioned earlier usually require a limitation of the
underreaching zone (normally zone 1) to 75 - 90% of the protected line.
In case of parallel lines, consider the influence of the mutual coupling according
tosection
"Parallel line application with mutual coupling"
and select the case(s) that
are valid in your application. We recommend to compensate setting for the cases
when the parallel line is in operation, out of service and not earthed and out of
service and earthed in both ends. The setting of earthed fault reach should be
selected to be <95% also when parallel line is out of service and earthed at both
ends (worst case).
8.5.3.3
Setting of overreaching zone
SEMOD154704-19 v4
The first overreaching zone (normally zone2) must detect faults on the whole
protected line. Considering the different errors that might influence the
measurement in the same way as for zone1, it is necessary to increase the reach of
the overreaching zone to at least 120% of the protected line. The zone2 reach can
be even higher if the fault infeed from adjacent lines at remote end are considerable
higher than the fault current at the IED location.
The setting shall generally not exceed 80% of the following impedances:
Section 8
1MRK 506 369-UEN B
Impedance protection
276
Line distance protection REL670 2.2 IEC
Application manual
Содержание REL670 2.2 IEC
Страница 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Страница 2: ......
Страница 32: ...26 ...
Страница 70: ...64 ...
Страница 110: ...104 ...
Страница 152: ...146 ...
Страница 564: ...558 ...
Страница 570: ...564 ...
Страница 592: ...586 ...
Страница 706: ...700 ...
Страница 804: ...798 ...
Страница 848: ...842 ...
Страница 860: ...854 ...
Страница 882: ...876 ...
Страница 896: ...890 ...
Страница 906: ...900 ...
Страница 907: ...901 ...