load
1.6 Z
RFPPZx
EQUATION579 V3 EN-US
(Equation 397)
is applicable only when the loop characteristic angle for the phase-to-
phase faults is more than three times as large as the maximum expected load-
impedance angle. More accurate calculations are necessary according to
equation
.
load min
R1Zx
RFPPZx
1.6 Z
cos
sin
X1Zx
IECEQUATION2307 V2 EN-US
(Equation 398)
All this is applicable for all measuring zones when no Power swing detection
function ZMRPSB is activated in the IED. Use an additional safety margin of
approximately 20% in cases when a ZMRPSB function is activated in the IED,
refer to the description of Power swing detection function ZMRPSB.
8.13.4.9
Zone reach setting higher than minimum load impedance
GUID-78D0227F-2568-4C9A-8921-45812B4ABAF2 v5
The impedance zones are enabled as soon as the (symmetrical) load impedance
crosses the vertical boundaries defined by
RLdFw
and
RLdRv
[9]
or the lines
defined by
ArgLd
. So, it is necessary to consider some margin. It is recommended
to set
RLdFw
and
RLdRv
to 90% of the per-phase resistance that corresponds to
maximum load.
min
0.9
load
RLdFw
R
<
×
IECEQUATION2419 V2 EN-US
(Equation 399)
min
0.9
load
RLdRv
R
<
×
IECEQUATION2420 V2 EN-US
(Equation 400)
The absolute value of the margin to the closest
ArgLd
line should be of the same
order, that is, at least 0.1 • Z
load min
.
The load encroachment settings are related to a per-phase load impedance in a
symmetrical star-coupled representation. For symmetrical load or three-phase and
phase-to-phase faults, this corresponds to the per-phase, or positive-sequence,
impedance. For a phase-to-earth fault, it corresponds to the per-loop impedance,
including the earth return impedance.
[9] RLdRv=RLdRvFactor*RLdFw
1MRK 506 369-UEN B
Section 8
Impedance protection
Line distance protection REL670 2.2 IEC
403
Application manual
Содержание REL670 2.2 IEC
Страница 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Страница 2: ......
Страница 32: ...26 ...
Страница 70: ...64 ...
Страница 110: ...104 ...
Страница 152: ...146 ...
Страница 564: ...558 ...
Страница 570: ...564 ...
Страница 592: ...586 ...
Страница 706: ...700 ...
Страница 804: ...798 ...
Страница 848: ...842 ...
Страница 860: ...854 ...
Страница 882: ...876 ...
Страница 896: ...890 ...
Страница 906: ...900 ...
Страница 907: ...901 ...