current of a line is close to zero and even can be zero. The operating value must
exceed the maximum charging current of an overhead line when only one phase is
disconnected (mutual coupling in the other phases).
UPh<
is used to set the voltage level for the detection of a dead line.
UPh<
is, by
default, set to 70% of
UBase
. This is a suitable setting in most cases, but it is
recommended to check the suitability in the actual application.
AutoInitMode
: automatic activating of ZCVPSOF is, by default, set to
DLD
disabled
, which means the dead-line logic detection is disabled. If an automatic
activation of the dead-line detection is required, the parameter
AutoInitMode
has to
be set to either
Voltage
,
Current
or
Current & Voltage
.
When
AutoInitMode
is set to
Voltage
, the dead-line detection logic checks that the
three-phase voltages are lower than the set
UPh<
level.
When
AutoInitMode
is set to
Current
, the dead-line detection logic checks if the
three-phase currents are lower than the set
IPh<
level.
When
AutoInitMode
is set to
Current & Voltage
, the dead-line detection logic
checks that both three-phase currents and three-phase voltages are lower than the
set
IPh<
and
UPh<
levels.
Otherwise, the logic is activated by an external
BC
input.
tSOTF
: the drop delay of ZCVPSOF is, by default, set to 1.0 seconds, which is
suitable for most applications.
tDLD
: The time delay for activating ZCVPSOF by the internal dead-line detection
is, by default, set to 0.2 seconds. It is suitable in most applications. The delay shall
not be set too short to avoid unwanted activations during transients in the system.
Mode
: The operation of ZCVPSOF has three modes for defining the criteria for
tripping. The setting of
Mode
is, by default,
UILevel
, which means that the tripping
criterion is based on the setting of
IPh<
and
UPh<
. The choice of
UILevel
gives a
faster and more sensitive operation of the function, which is important for reducing
the stress that might occur when energizing onto a fault. However, the voltage
recovery can be slow in some systems when energizing the line. Therefore, if the
timer
tDuration
is set too short, ZCVPSOF can interpret this as a fault and release a
trip.
When
Mode
is set to
Impedance
, the operate criterion is based on the
BC
input
(breaker closing), which can be the start of the overreaching zone from the
impedance zone measurement or a
tOperate
-delayed
START_DLYD
input. A
nondirectional output signal should be used from an overreaching zone. The
selection of the
Impedance
mode gives increased security.
When
Mode
is set to
UILvl&Imp
, the condition for tripping is an ORed between
UILevel
and
Impedance
.
Section 8
1MRK 506 369-UEN B
Impedance protection
444
Line distance protection REL670 2.2 IEC
Application manual
Содержание REL670 2.2 IEC
Страница 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Страница 2: ......
Страница 32: ...26 ...
Страница 70: ...64 ...
Страница 110: ...104 ...
Страница 152: ...146 ...
Страница 564: ...558 ...
Страница 570: ...564 ...
Страница 592: ...586 ...
Страница 706: ...700 ...
Страница 804: ...798 ...
Страница 848: ...842 ...
Страница 860: ...854 ...
Страница 882: ...876 ...
Страница 896: ...890 ...
Страница 906: ...900 ...
Страница 907: ...901 ...