To overcome the lower dependability in permissive schemes, an unblocking
function can be used. Use this function at older, less reliable, power line carrier
(PLC) communication, where the signal has to be sent through the primary fault.
The unblocking function uses a guard signal CRG, which must always be present,
even when no CR signal is received. The absence of the CRG signal during the
security time is used as a CR signal. This also enables a permissive scheme to
operate when the line fault blocks the signal transmission. Set the
tSecurity
to 35
ms.
16.6.3
Setting guidelines
M13920-4 v7
The parameters for the scheme communication logic for residual overcurrent
protection function are set via the local HMI or PCM600.
The following settings can be done for the scheme communication logic for
residual overcurrent protection function:
Operation
:
Off
or
On
.
SchemeType
: This parameter can be set to
Off
,
Intertrip
,
Permissive UR
,
Permissive OR
or
Blocking
.
tCoord
: Delay time for trip from ECPSCH function. For Permissive under/
overreaching schemes, this timer shall be set to at least 20 ms plus maximum reset
time of the communication channel as a security margin. For Blocking scheme, the
setting should be > maximum signal transmission time +10 ms.
Unblock
: Select
Off
if unblocking scheme with no alarm for loss of guard is used.
Set to
Restart
if unblocking scheme with alarm for loss of guard is used.
tSendMin
: Time duration, the carrier send signal is prolonged.
tSecurity
: The absence of CRG signal for a time duration of
tSecurity
is considered
as CR signal.
16.7
Current reversal and weak-end infeed logic for
residual overcurrent protection ECRWPSCH
IP14365-1 v4
16.7.1
Identification
M14883-1 v2
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Current reversal and weak-end infeed
logic for residual overcurrent protection
ECRWPSCH
-
85
1MRK 506 369-UEN B
Section 16
Scheme communication
Line distance protection REL670 2.2 IEC
723
Application manual
Содержание REL670 2.2 IEC
Страница 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Страница 2: ......
Страница 32: ...26 ...
Страница 70: ...64 ...
Страница 110: ...104 ...
Страница 152: ...146 ...
Страница 564: ...558 ...
Страница 570: ...564 ...
Страница 592: ...586 ...
Страница 706: ...700 ...
Страница 804: ...798 ...
Страница 848: ...842 ...
Страница 860: ...854 ...
Страница 882: ...876 ...
Страница 896: ...890 ...
Страница 906: ...900 ...
Страница 907: ...901 ...